Eight-Point Input And Eight-Point Output Units (E-Con Connectors) - Omron CRT1 - 10-2008 Operation Manual

Componet slave units and repeater unit
Table of Contents

Advertisement

Units with Connectors
5-4-5
Eight-point Input and Eight-point Output Units (e-CON
Connectors)
CRT1-MD16S/CRT1-MD16S-1/CRT1-MD16SH/CRT1-MD16SH-1
Common Specifications
Item
Model
Installation
Communications power supply cur-
rent consumption
Weight
Input Section Specifications
Item
Model
I/O capacity
Internal I/O common
ON voltage
OFF current
Input current
ON delay
OFF delay
Power supply short-circuit detection
Disconnection detection
Number of circuits per common
Isolation method
Input indicator
Power supply type
Power short-circuit protection
Current supplied to input devices
202
CRT1-MD16S
CRT1-MD16S-1
DIN Track
75 mA max. for 24-VDC power supply
voltage
95 mA max. for 14-VDC power supply
voltage
120 g max.
CRT1-MD16S
CRT1-MD16S-1
8 inputs
NPN
PNP
10.5 VDC min.
10.5 VDC min.
(between each
(between each
input terminal and
input terminal and
the V terminal)
the G terminal)
1.0 mA max.
At 24 VDC: 6.0 mA max./input
At 11 VDC: 3.0 mA min./input
1.5 ms max.
1.5 ms max.
---
---
8 inputs/common
Photocoupler
LED (yellow)
Network power supply
Operates at 50 mA/point min.
50 mA/input
Specification
CRT1-MD16SH
60 mA max. for 24-VDC power supply
voltage
90 mA max. for 14-VDC power supply
voltage
Specification
CRT1-MD16SH
NPN
10.5 VDC min.
(between each
input terminal and
the V terminal)
Operates at 50 mA/point min.
Operates at 0.3 mA/point max.
Section 5-4
CRT1-MD16SH-1
CRT1-MD16SH-1
PNP
10.5 VDC min.
(between each
input terminal and
the G terminal)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crt1 series

Table of Contents