Wiring Main Circuit Inputs - Omron CIMR-E7Z Quick Manual

200v class single-phase 0.4 to 110 kw; 400v class 3-phase 0.4 to 300 kw
Hide thumbs Also See for CIMR-E7Z:
Table of Contents

Advertisement

Wiring Main Circuit Inputs

Installing Fuses
To protect the inverter, it is recommended to use semiconductor fuses like they are shown in the
table below.
Rated Inverter
Inverter Type
Output
Current (A)
20P4
3.2
20P7
4.1
21P5
7.0
22P2
9.6
23P7
15
25P5
23
27P5
31
2011
45
2015
58
2018
71
2022
85
2030
115
2037
145
2045
180
2055
215
2075
283
2090
346
2110
415
40P4
1.8
40P7
2.1
41P5
3.7
42P2
5.3
43P7
7.6
44P0
8.7
45P5
12.5
47P5
17
4011
24
4015
31
4018
39
4022
45
4030
60
4037
75
4045
91
4055
112
4075
150
4090
180
4110
216
4132
260
4160
304
4185
370
4220
506
4300
675
Consider the following precautions for the main circuit power supply input.
If a moulded case circuit breaker is used for the power supply connection (R/L1, S/L2, and T/L3),
ensure that the circuit breaker is suitable for the Inverter.
Table 4 Input Fuse Selection
Fuse Selection
Voltage (V)
Current (A)
240
10
240
10
240
15
240
20
240
30
240
40
240
60
240
80
240
100
240
130
240
150
240
180
1500~23000
240
240
2100~19000
240
300
2700~55000
240
350
4000~55000
240
450
7100~64000
240
550
11000~64000
240
600
13000~83000
480
5
480
5
480
10
480
10
480
15
480
20
480
25
480
30
480
50
480
60
480
70
480
80
480
100
480
125
480
150
480
150
1500~13000
480
250
3000~55000
480
300
3800~55000
480
350
5400~23000
480
400
7900~64000
14000~25000
480
450
20000~25000
480
600
34000~40000
480
700
52000~92000
480
900
Selection Example (Ferraz)
2
2
Model
I
t (A
s)
12~25
A60Q12-2
12~25
A60Q12-2
23~55
A60Q15-2
34~98
A60Q20-2
82~220
A60Q30-2
220~610
A50P50-4
290~1300
A50P80-4
450~5000
A50P80-4
1200~7200
A50P125-4
500V / 125A
1800~7200
A50P150-4
500V / 150A
870~16200
A50P150-4
500V / 150A
A50P200-4
500V / 200A
A50P250-4
500V/ 250A
A50P300-4
500V / 300A
A50P350-4
500V / 350A
A50P450-4
500V / 450A
A50P600-4
500V / 600A
A50P600-4
500V / 600A
6~55
A60Q10-2
6~55
A60Q10-2
10~55
A60Q12-2
18~55
A60Q15-2
34~72
A60Q20-2
50~570
A60Q30-2
100~570
A60Q30-2
100~640
A60Q30-2
150~1300
A70P50-4
400~1800
A70P70-4
700~4100
A70P80-4
240~5800
A70P80-4
500~5800
A70P100-4
700V / 100A
750~5800
A70P125-4
700V / 125A
920~13000
A70P150-4
700V / 150A
A70P200-4
700V / 200A
A70P250-4
700V / 250A
A70P300-4
700V / 300A
A70P350-4
700V / 350A
A70P400-4
700V / 400A
A70P450-4
700V / 450A
0
A70P600-4
700V / 600A
0
A70P700-4
700V / 700A
0
A70P900-4
700V / 900A
0
2
2
Rating
I
t (A
s)
600V / 12A
17
600V / 12A
17
600V / 15A
26
600V / 20A
41
600V / 30A
132
500V / 50A
250
500V / 80A
640
500V / 80A
640
1600
2200
2200
4000
6200
9000
12000
20000
36000
36000
600V / 10A
10
600V / 10A
10
600V / 12A
17
600V / 15A
26
600V / 20A
41
600V / 30A
132
600V / 30A
132
600V / 30A
132
700V / 50A
300
700V / 70A
590
700V / 80A
770
700V / 80A
770
1200
1900
2700
4800
7500
11000
15000
19000
24000
43000
59000
97000
EN-12