Alderon Industries Go2 Simplex Quick Start Manual

Advertisement

GO2 - Single Phase, Simplex
Model: GO21S | Opaque Door, Beacon
QSG00409_Rev02_Go2 1P Simplex GO21S Series.pdf | September 13th, 2023 8:39am
Introduction
Product Overview
The Go2 Simplex control panel is designed to operate a single sewage pump in demand dose applications. It
supports both 120VAC and 230VAC pumps and features a high reliability power relay for controlling the pump as
well as Hand-Off-Auto control for the pump. The control panel is housed in a Type 4X (indoor/outdoor) enclosure
and includes an RG LED beacon for status indication.
The panel features three float inputs for the essential levels: stop level, start level, and high level. The pump starts
when the liquid level rises and activates the start level switch, and runs until the pump stop switch is deactivated,
ending the cycle. The high level float will trigger a high level alarm when activated.
Product Highlights
Below is a list of highlighted features of the Go2 Simplex system. For further details on each feature, please see
the rest of this document.
Power Inputs
120/230 VAC Board Power Input
120/230 VAC Pump Power Input
Sensor Inputs
Three Float Inputs
Stop, Start, and Alarm
User Inputs
Test/Silence Switch
Test/Config Switch (For Changing Field Settings)
Hand-Off-Auto Control for the Pump
Outputs
High Reliability Pump Power Relay
One Auxiliary Dry Contact Output
Indications

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Go2 Simplex and is the answer not in the manual?

Questions and answers

Summary of Contents for Alderon Industries Go2 Simplex

  • Page 1 The high level float will trigger a high level alarm when activated. Product Highlights Below is a list of highlighted features of the Go2 Simplex system. For further details on each feature, please see the rest of this document.
  • Page 2: Before Installation

    Red/Green Beacon for System Normal, Pump Run, and Alarm Indication Indicator LEDs for Each Sensor Input Pump Run Indicator LEDs Field Configurations Input Error Detection Automatic Alarm Reset High Float Redundant Start Enable Green System Normal Beacon Enable Before Installation Before proceeding with the installation or operation of the control panel read all instructions thoroughly, as well as comply with all Federal, State and Local Codes, Regulations and Practices.
  • Page 3 Description of Product Interface The following sections will describe all of the interface points with the Go2, including all buttons, indicator outputs, and sensor inputs for the system. Outside of the Panel Each Go2 panel is equipped with a test/silence switch, an Red-Green (RG) indicator LED, and a buzzer. The test/silence switch is used to activate an indicator test routine to verify the beacon, buzzer, and LED indicators are all functioning properly.
  • Page 4: Sensor Connections

    Sensor Connections Float Sensors The F1 through F3 inputs are designed for standard signal level gold contact floats. They are powered by an isolated 3.3 Volt low power and touch safe power source generated by the Go2 circuit board. How To Clear an Alarm If automatic alarm reset is disabled, the user must manually clear all alarm events.
  • Page 5: Available Settings

    4. Exit Without Saving; To exit without changing any settings, keep holding the Test/Config button until the fast blinking pattern moves through all of the indicator LEDs and the system returns to the test blinking pattern. The Test/Config button can now be released without changing any settings. Available Settings Indicator Factory...
  • Page 6 © 2023 Alderon Industries. All rights reserved. | Powered by Wiki.js...