DZ47sLES NAVIGATOR RESIDUAL CURRENT OPERATED CIRCUIT-BREAKER Series User Manual Please carefully read this User Manual before installing and operating the product, and keep this manual properly for future reference...
Page 3
Safety Notice Please carefully read this manual before the installation, operation, run, maintenance, and inspection of the product, and install and operate this product properly according to the contents of the instructions. Danger: ⚫ It is prohibited to operate the circuit breaker with your wet hands; ⚫...
Table of Contents 1 Main Purpose and Scope of Application………………………… ................2 Product Model and Its Meanings……………………………………………………………………......1 2.1 Product Model and Its Meanings…………………………………………………………......1 2.2 Panel Introduction………………………………………………………………………… ......2 3 Normal Working Conditions and Installation Conditions………………………………………… ......2 4 Technical Characteristics…………………………………………………………..........3 4.1 Classification……………………………………………………...
1 Main Purpose and Scope of Application DZ47sLES series residual current operated circuit breaker (hereinafter referred to as leakage circuit breaker) has electric leakage (electric shock), overload, and short circuit protection functions, and can also have over-voltage and under-voltage protection functions according to the needs of users. DZ47sLES leakage circuit breaker is used in the AC 50/60Hz lines with rated voltage 230V/400V and rated current up to 63A for indirect contact protection of people, as well as overcurrent protection for buildings and similar lines.
2.2 Panel Introduction Press before power-on Press once a month Load end Legends: 1 Inlet terminal 2 Company Logo 3 Product model (overvoltage model DZ47sLES G) 4 Trip curve and rated current (see Table 1) 5 Rated voltage (see Table 1) 6 Breaking capacity and frequency (see Table 1) 7 Reference standards 8 Certification marks 9 Identification on load end 10 N-pole marking 11 Reset button...
d) Installation conditions: The external magnetic field near the installation site of the residual current operated circuit breaker should not exceed 5 times of the geomagnetic magnetic field in any direction; the installation position should be vertical, and the inclination angle in any direction should not exceed 10° ; the product is installed in a place where there is no shock vibration and no rain or snow erosion;...
4.3 Main Technical Performance a) Overcurrent release protection characteristics see Table 2 Table 2 Overcurrent release protection characteristics Type of Rated overcurrent Test Starting Expected Reference current In Test time Remarks instantaneous current A state results temp. release type 1.13In Cold state t≤1h No trip...
Fig. 1 Outline and installation dimensions 6 Installation, Operation and Maintenance Check whether the product mark is consistent with the conditions used before installation; Correctly connect the wires at the inlet terminal and outlet terminal according to the product identification (the load current should be less than the rated current of the product);...
Table 3 Sectional-area and rated current of the connecting (copper) wire Rated current A 16, 20 40, 50 Sectional area of wire mm g) After power-on, operate the residual current operated circuit breaker test button several times and confirm whether it works reliably; ℃.
Mis-operation caused by zero line Only the phase line on the power connected of the residual side of the residual current operated Connect the zero line on the current operated circuit circuit breaker is connected, but the power side breaker zero line is not connected 8 Unpacking Inspection After unpacking, the user must check whether the product is intact, whether the exposed metal is rusty, and whether...
Page 12
Inspector: Check 06 DELIXI ELECTRIC LTD Date of production: See the label in the inner box DELIXI ELECTRIC LTD Delixi Industrial Park, Liushi Town, Yueqing City, Zhejiang Province P/C.: 325604 Tel: (86-577)6177 8888 Fax: (86-577)6177 8000 Customer service hotline: 400-826-8008 www.delixi-electric.com...