Data Types And Formats; Cim Port Configuration - THOMSON REMOTE COMMUNICATION - V3.0 User Manual

Remote communication system
Table of Contents

Advertisement

SECTION 3
7.

Data Types And Formats

The following table describes the possible return data types and formats for Modbus
registers defined in the CIM.
A register data value consists of two bytes: the most significant (MSB) and the least
significant (LSB). Data values are arranged with the MSB first (called big-endian).
Data
Register
Maximum
Type
Count
Range
0 or non-
boolean 1
zero
0 to max-
enum
1
range
uint8
1
0-255
uint16
1
0-65535
string
n
special
struct
n
special
8.

CIM Port Configuration

Register
Field
(decimal)
Port#2
40257
Bitrate
Port#2
40258
Bits/char
Port#2
40259
Stopbits
Port#2
40260
Parity
Port#2 Rx
40261
Timeout
Port#2 Line
40262
Protocol
PM055 Rev 2 00/08/31
boolean value: 0=false, non-zero=true
enumeration: range from 0 to some maximum
unsigned 8-bit integer (allowable values can be
further limited)
unsigned 16-bit integer (allowable values can be
further limited)
character (0-255) string, ordered: MSB1, LSB1,
MSB2, LSB2, ...
structure; definition depends on register range;
ordered: MSB1=byte0, LSB1=byte1, MSB2=byte2,
LSB2=byte3, ...
Address
Register
Data
(hex)
Count
Format
100
1
enum
101
1
uint8
102
1
uint8
103
1
enum
104
1
uint16 0 to 65535 (20)
105
1
enum
54
Description
Value
0=57600, 1=38400,
2=19200, 3=14400, 4=9600,
5=4800, 6=2400, 7=1200
7 to 8 (8)
1 to 2 (1)
0=Odd, 1=Even, 2=None,
3=Mark, 4=Space
0=RS-232, 1=RS-422,
2=RS-485, 3=auto-detect
CIM PROTOCOL
Thomson Technology

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cim 3.0

Table of Contents