THOMSON REMOTE COMMUNICATION - V3.0 User Manual page 52

Remote communication system
Table of Contents

Advertisement

SECTION 2
An RS-232 to RS-422 converter is required to convert the signal from the computer or modem.
The required wiring from the RS-422 side of the convert to the RJ-45 connection on the
controller is as shown:
RS-232
To modem or
computer
The RS-232 NULL connection between the modem and the converter must pass all handshake
signals, as shown in the following diagram:
Signal/Pin
DB-9
TD
3
RD
2
RTS
7
CTS
8
DSR
6
CD
1
DTR
4
GND
5
The modem must store configuration in a non-volatile storage medium (such as FLASH). The
modem must be configured for the following features:
auto-answer,
connect at 4800 bps only (no fallback),
echo disabled,
no error correction,
no compression.
PM055 Rev 2 00/08/31
RS-422
TDB(+)
TDA(-)
RDA(-)
RDB(+)
GND
Converter
unused
Pin/Signal
3
TD
2
RD
7
RTS
8
CTS
6
DSR
1
CD
4
DTR
5
GND
46
THS 2000 SOFTWARE PROGRAM
RJ-45
1
2
3
To Controller
4
5
6
7
8
Signal/Pin
DB-25
TD
2
RD
3
RTS
4
CTS
5
DSR
6
CD
8
DTR
20
GND
7
Pin/Signal
2
TD
3
RD
4
RTS
5
CTS
6
DSR
8
CD
20
DTR
7
GND
Thomson Technology

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cim 3.0

Table of Contents