5.6.2. External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m (82 ft).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12 V ±2 V, Lo 0 V.
• Permissible current: 50 mA
Output select
● When interlocking with external device
Connected
device
Relay (locally purchased)
● When displaying "Operation/Stop"
Resistor
Connected device
5.6.3. Function setting for external input and output
NOTE:
Inappropriate setting may cause an external device malfunction. Confirm whether all the
settings have been performed appropriately according to the installing condition.
Setting
Function
number
External input
number
(♦: Default)
00 ♦
Start/Stop
01
Emergency stop
02
Forced stop
03 to 09
10
Start/Stop (logic inverse)
46
11
Emergency stop (logic inverse)
12
Forced stop (logic inverse)
(External
13
control)
Allow an external controller to start or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed from an external controller, all refrig-
erant systems will be disabled.
* If forced stop is set, indoor unit stops by the input to the external input
terminals, and Start/Stop by a remote controller is restricted.
Operation/Stop, Emergency
stop or Forced stop
00 ♦
For operation behavior, refer to
"5.6.1. External input".
01 to 08
Refrigerant leak detection
OFF → ON
09 (*1)
ON → OFF
10 to 12
60
Operation/Stop, Emergency
(Switching
stop or Forced stop
13
function for
For operation behavior, refer to
external
"5.6.1. External input".
input and
Operation/Stop, Emergency
output)
stop or Forced stop
14
For operation behavior, refer to
"5.6.1. External input".
Operation/Stop, Emergency
stop or Forced stop
15
For operation behavior, refer to
"5.6.1. External input".
*1: Only for R410A system J-IIIL/J-IVL series
P.C.B.
CN47
P.C.B.
CN47
External output
Prohibited
Prohibited
Operation/stop
0 V
Stop
DC 12 V Operation
Prohibited
External heater
No command
0 V
Heater off
Refrigerant leak
DC 12 V Heater on
Prohibited
Error display
0 V
Normal
DC 12 V Error
Fan output interlocking
Indoor unit fan
0 V
stop
Indoor unit fan
DC 12 V
operation
External heater
0 V
Heater off
DC 12 V Heater on

5.7. Remote sensor (Optional parts)

Connection method
• Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
• The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
• Use conduit hole when external output cable is used.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below. Refer to "6.3. Function setting" for details about Function number and Setting
number.
• Function Number "30": Set the Setting Number to "00". (Default)
• Function Number "31": Set the Setting Number to "02".
NOTE:
For optional parts not listed here, refer to the installation manuals included with each
optional part.

6. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows. Set by either of
the methods. Each setting method is described in below (1) to (3).
(1) IU AD, REF AD SW settings: This section (6.1. Setting the address)
(2) Remote controller settings:
Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting
information. (Set IU AD, REF AD SW to 0)

6.1. Setting the address

Manual address setting method
The indoor unit address and the refrigerant system address can also be set up through
the wireless remote controller
Be sure to turn OFF the power before performing the field setting.
Position and detail of the
switches
You need to remove the front
panel. Refer to "8. FRONT
PANEL REMOVAL AND IN-
STALLATION".
For refrigerant
system address
For indoor unit
address
• Set it according to the following procedures when setting manually.
6.1.1 Indoor unit address
• Rotary switch (IU AD × 1)....Factory setting "0"
• Rotary switch (IU AD × 10)....Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A
CAUTION
CAUTION
Use an insulated screwdriver
to set the dip switches.
Be careful not to make mis-
takes for switch settings.
En-10