Remote Sensor (Optional Parts); Ir Receiver Unit (Optional Parts); Field Setting; Setting The Address - Fujitsu AIRSTAGE ARXC036GTEH Installation Manual

Indoor unit duct type
Hide thumbs Also See for AIRSTAGE ARXC036GTEH:
Table of Contents

Advertisement

[In the case of "Pulse" input]
Connector
Ch1
CNA01 or CNA02
Ch2
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
"Operation/Stop" mode or "Emergency stop" mode, "Forced stop" mode can be selected
with function setting of indoor unit.
● Forced thermostat off function
["Edge" input only]
Function
Connector
setting
Ch3 of CNA03 or
60-00
CNA04
● Refrigerant leak detection function (only for J-IIIL series)
["Edge" input only]
Function
Connector
setting
Ch3 of CNA03 or
60-09
CNA04
(2) External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
● When indicator etc. are connected directly
Operation
indicator
Error
indicator
Indoor unit Fan
status indicator
connected unit
● When connecting with unit equipped with a power supply
Connected
device 1
Connected
device 2
Connected
device 3
connected unit
Relay (locally purchased)
Operation behavior
Connector
External output1
Pins 1-2
External output2
CNB01
Pins 1-3
External output3
Pins 1-4
Input signal
Command
OFF → ON
Forced stop
OFF → ON
Normal
Input signal
Command
OFF → ON
Thermostat off
ON → OFF
Normal
Input signal
Command
OFF → ON
No command
ON → OFF
Refrigerant leak
P.C.B
P.C.B
Output voltage
Status
0V
Stop
DC 12 V
Operation
0V
Normal
DC 12 V
Error
0V
Indoor unit fan stop
DC 12 V
Indoor unit fan operation

6.7. Remote sensor (Optional parts)

• For the installation method, please refer to the INSTALLATION MANUAL of remote
sensor.
Connection methods
• Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
• The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
• Use conduit hole when external output cable is used.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
• Function Number "30":
Set the Setting Number to "00". (Default)
• Function Number "31":
Set the Setting Number to "02".
* Refer to "7.4. Function setting" for details about Function
Number and Setting Number.

6.8. IR receiver unit (Optional parts)

Connection method
• For the installation method, please refer to the INSTALLATION MANUAL of IR receiver
unit.
(1) Use 9 pins for receiver unit cable.
(2) At first, connect the receiver unit cable to the controller PCB.
(3)
Attach the core that comes between controller PCB and the clamp.
(4) Use conduit hole when external output cable is used.

7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings .............. This section (7.1. Setting the address)
(2) Remote controller settings ............... Refer to the wired or wireless remote controller
(3) Automatic address settings ............. Refer to the outdoor unit manual for detailed
CNB
Be sure to turn OFF the power before performing the fi eld setting.
01

7.1. Setting the address

Manual address setting method
• If the receiver unit is attached, the indoor unit address and the refrigerant circuit
address can also be set up through the wireless remote controller.
Use an insulated screwdriver to set the DIP switches.
For indoor
CNB
unit address
01
Setting
Indoor unit address
Refrigerant circuit
address
(1) Indoor unit address
Rotary switch (IU AD × 1)...Factory setting "0"
Rotary switch (IU AD × 10)...Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1)...Factory setting "0"
Rotary switch (REF AD × 10)...Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
manual for detailed setting information. (Set IU
AD, REF AD SW to 0)
setting information. (Set IU AD, REF AD SW to 0)
CAUTION
CAUTION
For refrigerant
circuit address
IU AD
REF AD
RC AD
×10
×1
×10
×1
SET3
SET4
Setting
Type of switch
range
Setting
0 to 63
example 2
IU AD × 10
Setting
0 to 99
example 63
REF AD × 10
IU AD × 1
REF AD × 1
En-10

Advertisement