6.3.1 Indoor unit indicator lamps
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
FILTER indicator lamp (red)
6.3.2 Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indoor unit address
OPERATION indicator lamp (Green)
ON
TIMER indicator lamp (Orange)
Address: tens place (0.5 s ON/0.5 s OFF)
FILTER indicator lamp (Red)
Address: ones place (0.5 s ON/0.5 s OFF)
(Example) Indoor unit address: 24
ON
OPERATION indicator
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5
0.5
s
s
(Orange)
OFF
ON
FILTER indicator lamp
0.5
0.5
s
s
(Red)
OFF
(Example) Refrigerant system address: 30
ON
OPERATION indicator
1.0 s 1.0 s
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5
0.5
s
s
(Orange)
OFF
ON
FILTER indicator lamp
(Red)
OFF
Setting details
Function number
01
Indoor unit address
02
Refrigeration address
For use with a remote controller, set all rotary switches to 0, and refer to "6.1. Setting the
address" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
(Example) Function number: 31, Setting number: 2
ON
OPERATION indicator
0.5
0.5
s
s
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5
0.5
s
s
(Orange)
OFF
ON
FILTER indicator lamp
0.5
0.5
s
s
(Red)
OFF
Indication pattern
Refrigerant address
Blink (1.0 s ON/1.0 s OFF)
1 cycle 12 seconds
ON
0.5
0.5
10 s
s
s
0.5
0.5
0.5
0.5
0.5
0.5
8 s
s
s
s
s
s
s
1 cycle 12 seconds
1.0 s
1.0 s
1.0 s
1.0 s
1.0 s
0.5
0.5
0.5
0.5
9 s
s
s
s
s
OFF
Item
Setting number
00 to 63
00 to 99
Indication pattern
Function number; tens place (0.5 s ON/0.5 s OFF)
Function number; ones place (0.5 s ON/0.5 s OFF)
Setting number: (0 to 9) (0.5 s ON/0.5 s OFF)
1 cycle 12 seconds
0.5
0.5
0.5
0.5
9 s
s
s
s
s
11 s
0.5
0.5
10 s
s
s

7. FINISHING

After checking for gas leaks (refer to the installation manual of the outdoor unit), perform
this section.
Install thermal insulation around both the large (gas) and small (liquid) pipes. Failure to
do so may cause water leaks.

7.1. Connection pipe, cable and drain hose

Insulate the drain hose, if necessary, to prevent it from freezing.
(1) Insulate between pipes.
• For (A) Rear, (B) Right and (C) Bottom piping, overlap the connection pipe thermal
insulation and indoor unit pipe thermal insulation and bind them with vinyl tape so that
there is no gap.
• For (D) Left bottom piping, (E) Left piping, (F) Left rear piping, butt the connection pipe
thermal insulation and indoor unit pipe thermal insulation together and bind them with
vinyl tape so that there is no gap.
((A) Rear, (B) Right and (C) Bottom piping)
Connection pipe
(thermal insulation)
Bind the pipes together so
that there is no gap.
Seal A is used when the diameter
of gas pipe is Ø12.70 or more.
(For (D) Left bottom piping, (E) Left piping, (F) Left rear piping)
• Wrap the area which accommodates the
rear piping housing section with cloth tape.
• Bind the connection cable with
Connection cable (Power supply cable)
vinyl tape.
• Bundle the piping and drain hose
together by wrapping them with
cloth tape over the range within
which they fit into the rear piping
housing section.
Connection cable
(Transmission and remote controller cable)
(2) Temporarily fasten the connection
cable along the connection pipe with
vinyl tape.
(3) Fasten the connection pipe to the
outside wall with a saddle, etc.
(4) Fill the gap between the outside wall
pipe hole and the pipe with sealer
so that rain water and wind cannot
blow in.
(5) Fasten the drain
hose to the outside
wall, etc.
Pipe
GOOD
Drain
hose
Saddle
Lifted up
CAUTION
Overlap the insulation.
Indoor unit pipe
(thermal insulation)
Vinyl tape
Butt connection pipe (thermal insulation)
against the indoor unit pipe (thermal insulation)
and wrap with seal A so that there is no gap.
Connection pipe
Indoor unit pipe
Wrap with cloth tape.
Cloth tape (Accessories)
Pipe
Vinyl tape
Wrap with cloth tape
Pipe
Cloth tape
Drain hose
Outside wall cap*
Saddle*
Sealer putty*
Wall
(Outdoors)
*Locally purchased
PROHIBITED
Wave
End in water
En-12