Technical specifications

The following table shows the technical specifications as of 11/2023. You will find a data
sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/ww/en/pv/6ES7516-3AP03-0AB0/td?dl=en).
Article number
Firmware version
Product function
Engineering with
Mains buffering
CPU 1516-3 PN/DP (6ES7516-3AP03-0AB0)
Equipment Manual, 11/2023, A5E46418484-AD
General information
Product type designation
HW functional status
FW update possible
I&M data
Isochronous mode
SysLog
STEP 7 TIA Portal configurable/integrated
from version
Configuration control
via dataset
Display
Screen diagonal [cm]
Control elements
Number of keys
Mode buttons
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Mains/voltage failure stored energy time
Repeat rate, min.
Input current
Current consumption (rated value)
Current consumption, max.
Inrush current, max.
I²t
6ES7516-3AP03-0AB0
 
CPU 1516-3 PN/DP
FS04
V3.1
Yes
 
Yes; I&M0 to I&M3
Yes; Distributed and central; with minimum OB
6x cycle of 375 µs (distributed) and 1 ms (cent­
ral)
Yes
 
V19 (FW V3.1) / V18 (FW V3.0) or higher; with
older TIA Portal versions configurable as
6ES7516-3AN02-0AB0
 
Yes
 
6.1 cm
 
8
2
 
24 V
19.2 V
28.8 V
Yes
 
5 ms
1/s
 
0.69 A
1.08 A
1.15 A; Rated value
0.6 A²·s
6
41