1-5. Rotation number of compressor limitation by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
• Cooling/Dry mode
Model name
AOUH30LUAH1
AOUH36LMAH1
AOUH48LMAH1

1-5. Rotation number of compressor limitation by outdoor temperature

K zone
122.0 °F
(50 °C)
J zone
114.8 °F
(46 °C)
I zone
107.6 °F
(42 °C)
H zone
100.4 °F
(38 °C)
G zone
87.8 °F
(31 °C)
F zone
55.4 °F
(13 °C)
E zone
44.6 °F
(7 °C)
D zone
35.6 °F
(2 °C)
C zone
23.0 °F
(-5 °C)
B zone
14.0 °F
(-10 °C)
A zone
Outdoor temperature zone
A zone
B zone
C zone
D zone
E zone
F zone
G zone
H zone
I zone
J zone
K zone
A zone
B zone
C zone
D zone
E zone
F zone
G zone
H zone
I zone
J zone
K zone
- (04-5) -
Limitation of compressor
frequency
35 rps
28 rps
28 rps
22 rps
22 rps
10 rps
14 rps
18 rps
18 rps
18 rps
22 rps
27 rps
27 rps
25 rps
25 rps
18 rps
15 rps
23 rps
27 rps
32 rps
36 rps
40 rps
1. Rotation number control of compressor