1-4. Rotation number of compressor at normal start-up

¢ Model: AOUH30LUAH1
Rotation number of compressor soon after starting is controlled as below.
Rotation number X
Rotation number IX
Rotation number VIII
Rotation number VII
Rotation number VI
Rotation number V
Rotation number IV
Rotation number III
Rotation number II
Rotation numbery I
• Normal operation
Rotation
I
number
41
(rps)
1
Time (sec)
60
• Special operation
Rotation
I
number
41
(rps)
1
Time (sec)
120
NOTES:
• Normal operation:
– Cooling and dry mode
• Below 3 hours from the compressor stop and the compressor thermistor ≥ 59 °F (15 °C)
• After defrost operation
– Other than when the compressor starts for the first time since the breaker turns on
• Special operation:
– Other than the normal operation condition
– When the compressor starts for the first time since the breaker turns on
1-4. Rotation number of compressor at normal start-up
Time 1
Time 2
Time 3
II
III
IV
46
51
57
2
3
4
120
180
300
II
III
IV
46
51
57
2
3
4
185
245
365
Time 4
Time 5
Time 6
V
VI
60
72
5
6
420
480
V
VI
60
72
5
6
665
725
- (04-3) -
Time 7
Time 8
Time 9
VII
VIII
IX
81
91
100
7
8
9
540
600
660
VII
VIII
IX
81
91
100
7
8
9
785
845
905
1. Rotation number control of compressor
Time 10
X
110
10
720
X
110
10
1,060