Rotation Number Of Compressor Limitation By Outdoor Temperature - Fujitsu ARXG45KHTA Service Manual

Hide thumbs Also See for ARXG45KHTA:
Table of Contents

Advertisement

1-5. Rotation number of compressor limitation by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
• Cooling/Dry mode
Model name
AOYG45KRTA
AOYG54KRTA

1-5. Rotation number of compressor limitation by outdoor temperature

K zone
52°C
J zone
50°C
I zone
46°C
H zone
31°C
G zone
21°C
F zone
13°C
E zone
7°C
D zone
2
°C
C zone
-5
°C
B zone
-10°C
A zone
Outdoor temperature zone
A zone
B zone
C zone
D zone
E zone
F zone
G zone
H zone
I zone
J zone
K zone
- (04-4) -
Limitation of compressor
frequency
50 rps
47 rps
40 rps
30 rps
22 rps
20 rps
16 rps
16 rps
17 rps
23 rps
28 rps
1. Rotation number control of compressor