1-4. Rotation number of compressor at normal start-up

Rotation number of compressor soon after starting is controlled as below.
Rotation number VIII
Rotation number VII
Rotation number VI
Rotation number V
Rotation number IV
Rotation number III
Rotation number II
Rotation number I
• Normal operation
Rotation
I
number
25
(rps)
1
Time (sec)
90
• Special operation
Rotation
I
number
25
(rps)
1
Time (sec)
225
NOTES:
• Normal operation:
– Cooling and dry mode
• Below 3 hours from the compressor stop and the compressor thermistor ≥ 15 °C
• After defrost operation
– Other than when the compressor starts for the first time since the breaker turns on
• Special operation:
– Other than the normal operation condition
– When the compressor starts for the first time since the breaker turns on
1-4. Rotation number of compressor at normal start-up
Time 1
Time 2
Time 3
II
III
42
53
2
3
150
270
330
II
III
42
53
2
3
305
605
665
- (04-3) -
Time 4
Time 5
Time 6
IV
V
VI
61
65
75
4
5
6
390
450
IV
V
VI
61
65
75
4
5
6
725
785
Time 7
Time 8
VII
VIII
85
92
7
8
570
630
VII
VIII
85
92
7
8
855
1,000
1. Rotation number control of compressor