Configuring Units For Downflow (Vertical) Discharge - Carrier Performance 50VG-K Installation Instructions Manual

15.2+ seer2 2-stage packaged air conditioner system with puron (r-410a) refrigerant single and three phase 2-5 nominal tons (sizes 24-60)
Table of Contents

Advertisement

50VG-K: Installation Instructions
1-in. (25 mm) min.
Fig. 8 – Condensate Trap
Step 7 – Install Duct Connections
The design and installation of the duct system must be in accordance
with the standards of the NFPA for installation of non-residence type air
conditioning and ventilating systems, NFPA 90A or residence type,
NFPA 90B and/or local codes and ordinances.
Select and size ductwork, supply-air registers, and return air grilles
according to ASHRAE (American Society of Heating, Refrigeration,
and Air Conditioning Engineers) recommendations. The unit has duct
flanges on the supply- and return-air openings on the side of the unit.
When designing and installing ductwork, consider the following:
1. All units should have field-supplied filters or accessory filter rack
installed in the return-air side of the unit. Recommended sizes for
filters are shown in
Table
2. Avoid abrupt duct size increases and reductions. Abrupt change in
duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and unit to
prevent transmission of vibration. Use suitable gaskets to ensure
weather-tight and airtight seal. When electric heat is installed, use
fireproof canvas (or similar heat resistant material) connector between
ductwork and unit discharge connection. If flexible duct is used, insert a
sheet metal sleeve inside duct. Heat resistant duct connector (or sheet
metal sleeve) must extend 24-in. (610 mm) from electric heater element.
3. Size ductwork for cooling air quantity (cfm). The minimum air
quantity for proper electric heater operation is listed in
Heater limit switches may trip at air quantities below those
recommended.
4. Seal, insulate, and weatherproof all external ductwork. Seal,
insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and Air
Conditioning Contractors National Association (SMACNA) and
Air Conditioning Contractors Association (ACCA) minimum
installation standards for residential heating and air conditioning
systems.
5. Secure all ducts to building structure. Flash, weatherproof, and
vibration-isolate duct openings in wall or roof according to good
construction practices.

Configuring Units for Downflow (vertical) Discharge

WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before performing service or maintenance operations on the system,
turn off main power to unit and install lockout tag. There may be more
than one disconnect switch.
1. Open all electrical disconnects and install lockout tag before
starting any service work.
2. Remove horizontal (metal) ductcovers to access vertical
(downflow) discharge duct knockouts in unit basepan. (See
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
TRAP
OUTLET
2-in. (51 mm) min.
1.
To remove downflow return and supply knockout covers, break front and
right side connecting tabs with a screwdriver and hammer. Push cover
down to break rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an electrical
knockout. Reinstall horizontal duct covers
factory. Insure openings are air and watertight.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence-type air conditioning and ventilating systems, NFPA 90A
or residence-type, NFPA 90B; and/or local codes and ordinances.
Adhere to the following criteria when selecting, sizing, and installing the
A09052
duct system:
1. Units are shipped for side shot installation.
2. Select and size ductwork, supply-air registers, and return-air grilles
according to American Society of Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE) recommendations.
3. Use flexible transition between rigid ductwork and unit to prevent
transmission of vibration. The transition may be screwed or bolted
to duct flanges. Use suitable gaskets to ensure weather-tight and
airtight seal.
4. All units must have field-supplied filters or accessory filter rack
installed in the return-air side of the unit. Recommended sizes for
filters are shown in
5. Size all ductwork for maximum required airflow (either heating or
cooling) for unit being installed. Avoid abrupt duct size increases or
decreases or performance may be affected.
6.
Adequately insulate and weatherproof all ductwork located
outdoors. Insulate ducts passing through unconditioned space, and
use vapor barrier in accordance with latest issue of Sheet Metal and
Air Conditioning Contractors National Association (SMACNA)
and Air Conditioning Contractors of America (ACCA) minimum
installation standards for heating and air conditioning systems.
Secure all ducts to building structure.
7. Flash, weatherproof, and vibration-isolate all openings in building
structure in accordance with local codes and good building
practices.
Table
2.
Fig.
9.)
9
(Fig.
9) shipped on unit from
Table
1.

Advertisement

Table of Contents
loading

Table of Contents