Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil
accumulations annually. Detecting oil generally indicates a refrigerant
leak.
CAUTION
!
EXPLOSION, SAFETY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
This system uses Puron (R-410A) refrigerant which has higher
operating pressures than R-22 and other refrigerants. No other
refrigerant may be used in this system. Gauge set, hoses, and recovery
system must be designed to handle Puron (R-410A). If you are unsure,
consult the equipment manufacturer.
If oil is detected or if low cooling performance is suspected, leak-test all
refrigerant tubing using an electronic leak-detector, halide torch, or
liquid-soap solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low cooling performance is
suspected, refer to Checking and Adjusting Refrigerant Charge section.

Evaporator Airflow

The heating and/or cooling air-flow does not require checking unless
improper performance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are open and free from obstructions, and
that the air filter is clean. When necessary, refer to Indoor Airflow and
Airflow Adjustments section to check the system airflow.

Puron (R-410A) Items

The indoor metering device is a TXV type device.

Pressure Switches

Pressure switches are protective devices wired into the control circuit
(low voltage). They shut off compressor if abnormally high or low
pressures are present in the refrigeration circuit. These pressure switches
are specifically designed to operate with Puron (R-410A) systems. R-22
pressure switches must not be used as replacements for the Puron
(R-410A) air conditioner.

Low-Pressure Switch (Air Conditioner Only)

This switch is located on the suction line and protects against low
suction pressures caused by such events as loss of charge, low airflow
across indoor coil, dirty filters, etc. It opens on a pressure drop at about
50 psig (957 Pa). If system pressure is above this, switch should be
closed.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohmmeter leads across switch. You should have continuity
on a good switch.
NOTE: Because these switches are attached to refrigeration system
under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem exists.
If switch must be removed, remove and recover all system charge so that
pressure gauges read 0 psi (0 Pa). Never open system without breaking
vacuum with dry nitrogen.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

High-Pressure Switch

The high-pressure switch is located in the discharge line and protects
against excessive condenser coil pressure. It opens at 650 psig (31.1
kPa). High pressure may be caused by a dirty condenser coil, failed fan
motor, or condenser air recirculation.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohmmeter leads across switch. You should have continuity
on a good switch.
Copeland Scroll Compressor (Puron [R-410A]

Refrigerant)

The compressor used in this product is specifically designed to operate
with Puron (R-410A) refrigerant and cannot be interchanged.
The compressor is an electrical (as well as mechanical) device. Exercise
extreme caution when working near compressors. Power should be shut
off, if possible, for most troubleshooting techniques. Refrigerants
present additional safety hazards.
!
FIRE/EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death
and/or property damage.
Wear safety glasses and gloves when handling refrigerants. Keep
torches and other ignition sources away from refrigerants and oils.
The scroll compressor pumps refrigerant throughout the system by the
interaction of a stationary and an orbiting scroll. The scroll compressor
has no dynamic suction or discharge valves, and it is more tolerant of
stresses caused by debris, liquid slugging, and flooded starts. The
compressor is equipped with a noise reducing shutdown device and an
internal pressure relief port. The pressure relief port is a safety device,
designed to protect against extreme high pressure. The relief port has an
operating range between 550 (26.3 kPa) and 625 (29.9 kPa) psig
differential pressure.
Refrigerant
!
EXPLOSION, ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
This system uses Puron (R-410A) refrigerant which has higher
operating pressures than R-22 and other refrigerants. No other
refrigerant may be used in this system. Gauge set, hoses, and recovery
system must be designed to handle Puron (R-410A). If you are unsure,
consult the equipment manufacturer.
This system uses Puron (R-410A) refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be
used in this system. Gage set, hoses, and recovery system must be
designed to handle Puron (R-410A). If you are unsure, consult the
equipment manufacturer. Failure to use Puron (R-410A) compatible
servicing equipment or replacement components may result in property
damage or injury.

Compressor Oil

The Copeland scroll compressor uses 3MAF POE oil. If additional oil is
needed, use Uniqema RL32-3MAF. If this oil is not available, use
Copeland Ultra 32 CC or Mobil Arctic EAL22 CC. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE oils can absorb 15
times as much water as other oils designed for HCFC and CFC
28