Installation
Spur Connection
Figure 3.10
Figure 3.11
The Ethernet-APL field devices are connected through a pluggable 3-pin connector.
3.5

Grounding / Shielding

Danger!
Explosion hazard from wrong or missing grounding!
Wrong or missing grounding can cause sparks. This can ignite the surrounding potentially
explosive atmosphere.
Ground the device. Observe the grounding requirements for type of protection Ex i
according to IEC/EN 60079-14.
Ensure that external ground connections exist, are in good condition, and are not dam-
aged or corroded.
Caution!
Risk of electric shock or property damage from inadequate grounding!
If you fail to connect all metal parts of the device to protective local earth correctly, this could
result in potential equalization currents. These currents could hurt operating personnel or
cause property damage.
The grounding terminal is not a safety earth: Do not use the grounding terminal to ground
exposed metal parts.
Ground exposed metal parts of the device separately. Ensure that a correct grounding is
guaranteed at all times.
Grounding the Device
The grounding terminal is marked with "PA".
The device provides a grounding terminal to which an equipotential bonding conductor with a
minimum cross section of 4 mm
Connector with screw terminals
Connector with spring terminals
2
must be connected.
23