Co mp a c t R a ise d & F la t C o v e r P re p Ta b l e s * For Legacy UHT, ULT, UPT, & US T M o de l s 4401 Blue Mound Road Fort Worth, Texas 76106 (USA) Phone: 800.825.8220 | Service Fax: 817.740.6757 | E-mail: service@traulsen.com | Website: traulsen.com...
The serial tag is a permanently affixed label on which is Ft. Worth, TX 76106 recorded vital electrical and refrigeration data about your 800-825-8220 Traulsen product, as well as the model and serial number. MODEL: UHT27-L MODELO: This tag is located in the right interior compartment on all MODELE: standard models.
III. c - Installing/Adjusting Legs or Casters crating materials and make note on the carrier’s Bill Of 6” high legs are supplied standard for all Traulsen compact Lading describing the damage. A freight claim should undercounter and prep table units. These are shipped from be filed immediately.
It is important for the proper operation and longevity of your counter top. This flange has two screw holes. Screw the Traulsen unit that it have adequate provisions underneath for air two 1/4-20x5/8” screws (provided through the holes in supply to the compressor. There are no clearance requirements this front flange into the threaded holes in the front of the for the sides, rear or top.
IV. OPERATION & CONTROL IV. OPERATION & CONTROL (cont’d) IV. c - Adjusting Cabinet Setpoint IV. a - Prestart Checks Setpoint display and modification: The compressor must float freely before connecting to electrical power. The compressor motor is provided with •...
IV. OPERATION & CONTROL (cont’d) IV. d - Initiating a Defrost (cont’d) Resuming thermostatic cycle: When defrost is over, if DRN is greater than 0, all outputs will remain off for DRN minutes, in order for the ice to melt completely and the resulting water to drain.
Page 7
IV. OPERATION & CONTROL (cont’d) RANGE DESCRIPTION -58..SPH Minimum limit for SP setting. SPL...180° Maximum limit for SP setting. SPL... SPH Setpoint (value to be maintained in the room). REF; HEA Refrigerating (REF) or Heating (HEA) control mode. 1...10° Thermostat OFF -> ON differential. 0...10°...
Page 8
IV. OPERATION & CONTROL (cont’d) RANGE DESCRIPTION NO/YES Fans active during defrost. -58...180° Evaporator fan re-start temperature after defrost. 0...120min Maximum evaporator fan stop after defrost. NON; Fan mode during thermostatic control. TMP; NON : The fans remain ON all the time; TMP : Temperature-based control.
Page 9
IV. OPERATION & CONTROL (cont’d) RANGE DESCRIPTION NON; Door switch input mode: ALR; NON : door switch inhibited ALR : when DIx=DOR and the digital input is on, an alarm is generated after ADO minutes STP : when DIx=DOR and the digital input is on, in addition to the alarm, the fans are immedi- ately stopped and the compressor is stopped after CSD minutes.
IV. OPERATION & CONTROL (cont’d) RANGE DESCRIPTION -12.5..12.5° Probe 3 offset. NON; Operation in case of high condenser alarm ALR; NON : high condenser alarm inhibited. STP; ALR : in case of alarm, “HC” flashes in the display and the buzzer is switched on. STP : in addition to the alarm symbols displayed, the compressor is stopped and defrosts are suspended.
IV. OPERATION & CONTROL (cont’d) V. CARE AND MAINTENANCE IV. h - Refrigerating Product WARNING: DISCONNECT ELECTRICAL POWER SUPPLY BEFORE CLEANING ANY PARTS OF THE UNIT. A thermometer is provided inside all UHT, ULT, UPT & UST models. Allow the cabinet to reach normal operating V.
4401 Blue Mound Road Fort Worth, TX 76106 (800) 825-8220 If a leak is suspected, all naked flames shall be Traulsen reserves the right to change specifications or discontinue removed/extinguished. models without notice. If a leakage of refrigerant is found which requires...
VI. g - Warranty Registration position of being open 90° to the cabinet. Place the top hinge The warranty for your new Traulsen unit may be registered plate in the hole in the top of the door and support the other with us by completing warranty information online, via our end of the door for minimal movement.
VIII. TROUBLE SHOOTING GUIDE PROBLEM REMEDY a. Check if cord has been disconnected. 1. Condensing unit fails to start. b. Check control temperature setting. a. Are doors closing properly? 2. Condensing unit operates for b. Dirty condenser filter. Clean properly. prolonged periods or continuously.