Installing The Unit

Installation Guidelines
Make sure to follow below guides when installing at the seashore.
1.
Do not install the product in a place where it is directly exposed to sea water and sea breeze.
Make sure to install the product behind a structure (such as building) that can block see breeze
Even when it is inevitable to install the product in seashore, make sure that product is not directly
exposed to sea breeze by installing a protection wall.
2.
Consider that the salinity particles clinging to the external panels should be sufficiently washed out.
3.
Because the residual water at the bottom of the outdoor unit significantly promotes corrosion, make sure
that the slope does not disturb drainage.
Keep the floor level so that rain does not accumulate.
Be careful not to block the drain hole due to foreign substance
4.
When product is installed in seashore, periodically clean it with water to remove attached salinity.
5.
Make sure to install the product in a place that provides smooth water drainage. Especially, ensure that the
base part has good drainage.
6.
If the product is damaged during the installation or maintenance, make sure to repair it.
7.
Check the condition of the product periodically.
8.
All R32 models have a hydrophobic 'bluefin' coating as standard.
9.
The Outdoor unit must be checked 1 year after installation for signs of corrision, regardless of the
installation location.
If installed within 500m of the seashore, an anti-corrosion coating is recommanded with
*retreating effected areas every 2 years.
If installed within 500m~2km of the seashore, an anti-corrosion coating is optional. If coated, it
is recommended the unit is *retreated every 4 years. If not coated, it is recommended the unit is
*retreated every 2 years.
*Note: Retreating is an essential part of the Outdoor units annual service plan.
Depending on the condition of power supply, unstable power or voltage
may cause malfunction of the parts or control system. (Places using power
Do not install the Air to Water Heat Pump in following places
1.
The place where there is mineral oil or arsenic acid. There is a chance that parts may get damaged due to
burned resin.
2.
The capacity of the heat exchanger may reduce or the Air to Water Heat pump may be out of order.
3.
The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet. The
supply from electric generator, etc).