DIAGNOSTICS menu
Figure 70
DIAGNOSTICS menu details (continued) (see Figure 58, page 66 for access information)
Menu/Item
Run Times
Burner Time
Displays cumulative time the burner has been active (can be increased by user)
Rotate Time
Records the days of operation passed from the last time the Master boiler rotated the firing sequence.
Input 1 Time
Displays cumulative time that Input 1 has been closed (Or 0-10V ≥ 1 volt)
Input 2 Time
Displays cumulative time that Input 2 has been closed
Input 3 Time
Displays cumulative time that Input 3 has been closed
Network Time
Records time this boiler was running on a network call for heat generated by the Master boiler
Ignition Count
Displays total number of successful ignitions
Master-Shadow Comm
Boiler ID
Displays boiler control type and ID number
Linked to Master
Shows if control is currently linked to a Master control
Boilers on Network
Shows number of boilers currently on network
Requested to Run
Shows if this control is being requested to satisfy a network call
Shows whether the control is Network-P1, Network-P2, or NONE
Type
Requested Mod Rate
Rate coming from the Master
Displays maximum allowable boiler temperature
Max Boiler Temp
Boiler On Diff
Temperature differential from master boiler for network priorities
Boiler Off Diff
Temperature differential from master boiler for network priorities
Network Boilers
For multiple boilers only – See SlimFit Advanced manual
###%
Shows current rate of boiler
###F
Shows Boiler Out temperature of boiler
######
Shows priority being satisfied, updated based on active demand
######
Shows system type of call for heat, updated based on active demand
Shows the sequence position of that boiler in all the boilers available
# OF #
BLR#
Shows boiler number this data belongs to
Network Inputs
Boiler number
Displays boiler number
Inputs
Displays input's configuration and whether it is active. If input is active, it will be displayed in BOLD print
Software Versions
Display
Software version of the microprocessor on the display circuit board
Main Micro
Software version of the main microprocessor on the control circuit board
Second Micro
Software version of the second microprocessor on the control circuit board
TO RESET ALL
To reset all history counters to zero: Enter the DIAGNOSTICS menu. Then press and hold the left and
HISTORY COUNTERS
right arrows located below the control display. Hold for 5 seconds. This will cause ALL history to be
TO ZERO:
deleted. To maintain history, reset counters individually.
PAST ERRORS
Displays number of control faults
Control Fault
Displays cumulative ignition attempts. It is recommended that his be reset during yearly maintenance by holding down
Ignition Retries
the Left and Right arrows or by selecting this line and pressing the Enter button
Displays number of manual reset lockouts since last cleared
Manual Reset Cnt
Displays number of auto reset lockouts since last cleared
Auto Reset Cnt
Choose this to view the most recent error recorded
Lockout History 1
Displays the name of the fault that occurred
Fault Name
Displays the type of fault that occurred
Fault Type
76
commercial condensing gas
(continued)
— Boiler Manual
-
fired water boiler
Comment