Weil-McLain SlimFit 2 Series Manual page 67

Commercial condensing gas-fired water boilers
Hide thumbs Also See for SlimFit 2 Series:
Table of Contents

Advertisement

SlimFit
®
Series 2
Control operation and setup
Figure 59
SlimFit control settings available in BASIC MODE (see Advanced Manual for ADVANCED MODE settings)
Boiler Settings Menu
• Boiler Model
• Control Type
• High Altitude
• Manual Reset High Limit Temp
• WWSD Temp
• Adjust Outdoor
• Circulator Exercising
• Freeze Protect Circs
• Reset Factory Default
Priority 1 menu
• Inputs Assigned (non-selectable)
• System Type
• Target Mod Sensor (non-selectable)
• Target Adjust (non-selectable)
• Supply Max
• Supply Min (not available for DHW) *
• OD Reset Max (or Volts for Max) *
• OD Reset Min (or Volts for Min) *
• Boost Time *
Figure 60
System types available in BASIC MODE (each option shown with factory settings)
System Type
Fan-coil
Finned Tube Baseboard
Cast Iron Baseboard
Cast Iron Radiators
Radiant - slab on grade
Radiant - thin slab
Radiant - below floor
RADFLOOR
(staple up)
Radiant - above floor
RADFLOOR
(sleeper system)
Domestic Hot Water
Custom (user defined)
Part number 550-100-561/0224
commercial condensing gas
Available settings from CONTRACTOR MENU
Priority 2 menu
• Inputs Assigned (non-selectable)
• System Type
• Target Mod Sensor (non-selectable)
• Target Adjust (non-selectable)
• Supply Max
• Supply Min (not available for DHW) *
• OD Reset Max (or Volts for Max) *
• OD Reset Min (or Volts for Min) *
• Boost Time *
Priority 3 menu
• Inputs Assigned (non-selectable)
• System Type
• Target Mod Sensor (non-selectable)
• Target Adjust (non-selectable)
• Supply Max
• Supply Min (not available for DHW) *
• OD Reset Max (or Volts for Max) *
• OD Reset Min (or Volts for Min) *
• Boost Time *
* These items only appear in the menus if Target Adjust is active.
8-Character
3-Character
Abbreviation
Abbreviation
FAN-COIL
FCL
FIN BASE
FTB
IRONBASE
CIB
RADIATOR
CIR
RAD SLAB
RSG
RAD SLAB
RTS
RSU
RAF
DOMESTIC
DHW
XXXXXXXX
first three of
user input
(user input)
-
— Boiler Manual
fired water boiler
(continued)
Supply Max
OD Reset
Supply
°F
Min °F
Min °F
180
0
140
180
0
130
180
0
120
180
0
120
120
0
140
0
160
0
140
0
180
N/A
N/A
180
0
Assign Inputs menu
Input 1: TT1
• Priority 1, 2 or 3
• Source (TT1 or 0-10v)
• AUX PUMP/OUTPUT
• Off
Input 2: TT2
and
Input 3:TT3
• Priority 1, 2 or 3
• AUX PUMP/OUTPUT
• Off
Diagnostics menu
• See Figure 67, page 73 for details.
Maintenance Info menu
• See Figure 72, page 78 for details.
Set Date and Time menu
• See Figure 72, page 78 for details.
OD Reset
Run
Max °F
Boiler Pump
70
YES
70
YES
70
YES
70
YES
80
70
YES
80
70
YES
90
70
YES
90
70
YES
N/A
NO
70
70
YES
Run AUX
PUMP/
OUTPUT
YES
YES
YES
YES
YES
YES
YES
YES
NO
YES
67