Electrical Configuration - OCEANAIRE OWC QC Series Engineering, Installation And Service Manual

Deluxe portable water-cooled cooler with quick connect
Table of Contents

Advertisement

ELECTRICAL CONFIGURATION

All OWC QC Series units are equipped with a standard 10-foot long service cord
with plug configurations and receptacle requirements as shown in this chart. All
single phase OWC-QC units are equipped with LCDI (Leakage Current Detection &
Interruption) devices that serve as a means of electrical protection.
DO NOT USE THE LCDI AS AN ON/OFF SWITCH FOR THE UNIT
All 3-phase models are equipped with locking plugs for added connection
reliability. Refer to the chart below for plug and receptacle details for all OWC
models.
POWER SUPPLY CORD AND NOT REPAIRED
UNIT/MODEL
115 VOLT
OWC1811QC
208-230 VOLT SINGLE PHASE
OWC2412QC
OWC3612QC
208-230 VOLT SINGLE PHASE
OWC6012QC
208-230 VOLT 3-PHASE
OWC3632QC
208-230 VOLT 3-PHASE
OWC6032QC
460 VOLT 3-PHASE
OWC3634QC
OWC6034QC
CAUTION
A DAMAGED POWER SUPPLY CORD
MUST BE REPLACED WITH A NEW
PLUG CONFIGURATION
15A-125 VOLT
NEMA 5-15P
20A-250 VOLT
NEMA 6-20P
30A-250 VOLT
NEMA 6-30P
20A-250 VOLT
NEMA L15-20P
30A-250 VOLT
NEMA L15-30P
20A-460 VOLT
NEMA L16-20P
5
RECEPTACLE
NEMA 5-15R
NEMA 6-20R
NEMA 6-30R
NEMA L15-20R
NEMA L15-30R
NEMA L16-20R

Advertisement