OWC- QC series Deluxe Portable Water-Cooled Cooler With Quick Connect ENGINEERING, INSTALLATION AND SERVICE MANUAL 052-009 EISM-OWC-QC 02012024...
FORWARD This manual provides the user with basic details for the installation and operation of the Oceanaire OWC-QC’s spot coolers. It is recommended to read and fully understand the instructions outlined within this manual, before operating the unit. As with all commercial air conditioning equipment, it is recommended to have the OWC-QC sized and installed by a licensed specifying engineer and contractor, in accordance with all local and state codes.
GENERAL INFORMATION The OceanAire OWC-QC model is a portable water-cooled air conditioner designed for permanent or temporary spot cooling applications. The entire air conditioning unit has been built in an attractive sheet metal cabinet, equipped with heavy-duty casters for mobility. All OWC-QC models come with a 10-foot power cord for electrical connection and added mobility in service.
STANDARD FEATURES CABINET The OWC-QC cabinet is constructed of 18 gauge steel with a gray and blue polyester powder coated finish that will compliment any decor. The entire cabinet is insulated with sound- absorbing insulation for cool, quiet comfort. All units come equipped with swivel casters for portability and convenient set-up.
APPLICATIONS SPOT COOLER The OWC QC can be used in an open environment to cool specific objects or "spots". Spot Cooling is a convenient and economical way to provide air conditioning where cooling the entire space is not viable. Cool air is discharged from the units grille and is directed where it is needed.
ELECTRICAL CONFIGURATION All OWC QC Series units are equipped with a standard 10-foot long service cord with plug configurations and receptacle requirements as shown in this chart. All single phase OWC-QC units are equipped with LCDI (Leakage Current Detection &...
USE OF EXTENSION CORDS CAUTION FOR MODEL OWC1811QC AN EXTENSION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 15 AMPS @ 115 VOLTS WITH GROUNDING-TYPE ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING) FOR MODELS OWC2412QC and OWC3612QC AN EXTENSION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 20 AMPS @ 250 VOLTS WITH GROUNDING-TYPE ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING)
OWC QC INTERIOR Blower Wheel Digital Controller Motor Evaporator Coil Compressor Condensate Pump High Pressure Switch Reset Button High Pressure Switch Reset Button Water Water Water Drain Water Drain Cubby for the Hose Kit Drain (OWC18/24QC) Cubby for the Hose Kit (OWC36/60 QC)
BEFORE INSTALLING Check the unit for any damage. All Oceanaire products are thoroughly inspected at the factory and carefully packaged. If any damage is evident, contact Oceanaire IMMEDIATELY.
Page 11
OWC QC Optional ACCESSORIES NOZZLE KIT 2NK-2 (2 X 6-Inch) OWC18QC, 24QC 2NK-3 (2 X 8-Inch) OWC36QC, OWC60QC EVAPORATOR RETURN AIR PLENUM 2DEP-12 (12-Inch Round) OWC18QC, 24QC DEP-16 (16-Inch Round) OWC36QC, 60QC DISCHARGE DUCT ADAPTER 2DDA-10 (10-Inch Round) OWC18QC, 24QC 2DDA-16 (16-Inch Round) OWC36QC, 60QC The 2DDA is a field installed duct adapter that...
Page 12
QC ACCESSORIES DISCHARGE AIR NOZZLE KIT ASSEMBLY The optional discharge nozzle kits are used to direct the conditioned air to a specific target area. By concentrating the airflow, the nozzles increase the air velocity towards production lines to cool personnel and/or equipment. In server rooms, the nozzles can be used to direct the airflow through the rack to remove the hot air from the area of the equipment.
Page 13
QC ACCESSORIES EVAPORATOR RETURN AIR PLENUM Evaporator return air plenums are available for installations where it is required to duct air to the inlet of the evaporator. The evaporator return air plenums allow the user to connect round duct (flexible or rigid) to the return air intake to reduce air noise and increase the number of options for solving difficult cooling problems.
Page 14
QC ACCESSORIES DISCHARGE DUCT ADAPTER Discharge duct adapters are available for applications where ducted evaporator discharge is required. The adapters can be easily installed on the unit without fasteners, and be installed for either vertical or horizontal ducting. The standard discharge grille is removed and the adapter is attached in the grille opening.
HK-QC Series Deluxe Hose Kit For All OWC-QC MODELS All OceanAire Quick-Connect (QC) hose kits are designed for use with OceanAire Portable Water- cooled Air conditioners equipped with Quick- Connect Fittings, to accommodate almost any installation requirement. The hose kit allows for...
HK-QC Series Hose Kits INSTALLATION INSTRUCTIONS 1. Connect Hose Kit to unit by aligning the QC Coupling with the QC Fitting on the unit. Connect the hose kit according to hose and unit labels: BLACK to WATER IN, RED to WATER OUT and YELLOW to DRAIN. HOLD the coupling behind the sleeve allowing the sleeve to move freely and PRESS firmly, until the sleeve retracts and clicks.
HA-QC HOSE ADAPTER KIT The Hose Adapter Kit allows for the installation of a OWC QC series water cooled unit where the Standard QC Hose Kit cannot accommodate the installation. The kit provides a means of connecting hoses to a QC-Model unit when the water source and drain are located in separate areas, or where longer hose runs are desired.
POWER button OCEANAIRE DELUXE ELECTRONIC CONTROLLER When power is connected, the controller will display “888” momentarily, and then disappear. Press the POWER button, then scroll drown to the TEMP SELECT button until the SET POINT is displayed. Adjust the SET POINT to the desired temperature, and the unit will cool as required.
Page 19
CONTROLLER PROGRAMMING MENU 1) Make sure the unit has power . 2) Press the power button “OFF”. “S-U-D-S” 3) Press the following buttons in sequence elect— p arrow — own arrow — elect) 4) The display will begin flashing P1 and a number. If there is no display, repeat the sequence, making sure the unit has power, but is turned OFF.
Page 20
P1 = 85, P2 = 40 OWC60 QC P1 = 85, P2 = 45 NOTICE Program Parameters are NOT controller default values. They are Oceanaire Factory Settings DISPLAY FAULTS LAC……………………. Low AC line power or communication problem between internal components.
WATER VALVE ADJUSTMENT Each OCEANAIRE WATER-COOLED unit is equipped with an automatic water regulating valve to control the condenser water flow rate. The water valve will open when the unit is in the cooling mode and adjust the gallon per minute flow rate based on the entering water temperature (EWT).
QC DELUXE SERIES WATER COOLED TROUBLESHOOTING TIPS techsupport@oceanaire-inc.com (847) 583-0311 NO DISPLAY check power @ wall outlet *check LCDI reset on cord end (if equipped) *re-seat display cable’s RJ connector on backside of controller *re-seat other end of display cable in power module (pcb) display port...
REPLACEMENT PARTS PROCEDURE IT IS RECOMMENDED THAT ALL OCEANAIRE UNITS BE SERVICED BY A LICENSED TECHNICIAN WARNING —TO AVOID INJURY, DISCONNECT UNIT POWER PRIOR TO SERVICING A. FAN MOTOR 1. Remove cabinet left-side panel (when looking at the front of the unit).
10 minutes. Then rinsing clean with hot water and shaking excess moisture from filter. GENERAL Oceanaire products are NOT approved for outdoor use. Therefore, off-season storage should be When necessary maintenance steps outlined above are indoor, protected from weather conditions.
WIRING SCHEMATIC FOR OWC1811QC and OWC2412QC OUTSIDE TEMP SENSOR HP RESET SWITCH INSIDE TEMP SENSOR COOLING ONLY DISPLAY ALT AIR COMPRESSOR POWER MODULE LOW VOLTAGE LINE VOLTAGE CONDENSATE SAFETY SWITCH UNIT/MODEL PLUG CONFIGURATION RECEPTACLE 115 VOLT OWC1811QC NEMA 5-15R 208-230 VOLT SINGLE PHASE OWC2412QC NEMA 6-20R OWC3612QC...
Page 28
WIRING SCHEMATIC FOR OWC3612QC and OWC6012QC COND PUMP POWER MODULE OWC3612 OWC6012 www.oceanaire-inc.com DELUXE WATER-COOLED PORTABLE AIR CONDITIONER Receptacle Receptacle MODELS OWC3612(QC) - OWC6012(QC) 6-20 6-30 208-230 VOLT, SINGLE-PHASE...
Page 29
WIRING SCHEMATIC FOR OWC3632QC and OWC6032QC OWC3632 OWC6032 WATER-COOLED SPOT COOLER MODELS OWC3632, OWC6032(QC) 208-230 V / 3-PHASE RECEPTACLE RECEPTACLE L15-20 L15-30...
Page 30
WIRING SCHEMATIC FOR OWC3634QC and OWC6034QC OUTSIDE TEMP SENSOR HEAT/COOL HP RESET SWITCH DISPLAY CEAN IRE INSIDE TEMP SENSOR FREON OAT/H20 VERIFY CORRECT ALT AIR DISPLAY POWER MODULE COMPRESSOR ROTATION 460V 3-Phase COMPRESSOR PUMP VALVE COMP COMP PUMP COMP CONTACTOR EVAP MOTOR Y-OUT...
LIMITED WARRANTY The Manufacturer (Oceanaire, Inc.) warrants to the original owner that the Product will be free from defects in material or workmanship for a period not to exceed one (1) year from date of installation. If upon examination by the Manufacturer, the...
END USER INFORMATION MODEL: SERIAL NUMBER: Date Purchased: Purchased from: Date Installed: For Technical Support or service parts, Keep Cool Team contact our at 847-583-0311 In order to receive the benefits of our warranty, please register on-line at www.oceanaire-inc.com 052-009 EISM-OWC-QC 02012024...