Indoor Unit Installation

Concrete
Hole in anchor
Hole in plug
Suspension bolt(3/8" or M10)
Ceiling support
Not supplied
Washer(supplied)
Rubber
Fasten the nut
Level
Vinyl tube
14
E-
It is recommended to install the refnet joint before installing the indoor unit.
1
Place the pattern sheet on the ceiling at the spot where you want to
install the indoor unit.
N N
o o
t t
e e
N N
o o
t t
e e
Insert bolt anchors, use existing ceiling supports or construct a suitable
2
support as shown in figure.
Insert
3
Install the suspension bolts depending on the ceiling type.
C C
A A
U U
T T
I I
O O
N N
C C
A A
U U
T T
I I
O O
N N
4
Screw eight nuts to the suspension bolts making space for hanging
the indoor unit.
C C
C C
A A
A A
U U
U U
T T
T T
I I
I I
O O
O O
N N
N N
5
Check the level of the indoor unit by using a leveler or a vinyl tube filled
with water.
N A tilt of the indoor unit may cause malfunction of a built-in float switch and
water leaks.
6
Adjust the height of the indoor unit by using the gauge of dimensions.
N You should adjust the gauge of dimensions and the pattern sheet to fit
the cutting dimensions of ceiling.
N Make sure that the indoor unit is installed at a level if the indoor unit
slants too much, there can be water leaks.
MH✴✴✴FKEA
Air
outlet
inlet
Gauge of Dimensions Ceiling
7
Tighten the upper part nuts.
8
Remove the gauge of dimensions after installing the indoor unit.
Since the diagram is made of paper, it may shrink or stretch slightly
due to temperature or humidity. For this reason, before drilling the
holes maintain the correct dimensions between the markings; refer
to pages 11~13.
N Ensure that the ceiling is strong enough to support the
weight of the indoor unit.
Before hanging the unit, test the strength of each
attached suspension bolt.
N If the length of suspension bolt is more than 1.5m, it is
required to prevent vibration.
N If this is not possible, create an opening on the false
ceiling in order to be able to use it to perform the
required operations on the indoor unit.
You must install the suspension bolts more than four
when installing the indoor unit.
MH✴✴✴FSEA/NJ✴✴✴1HXEA
Air
Air
outlet
inlet
Gauge of Dimensions Ceiling
MH✴✴✴FMEA
Indoor Unit
20mm
Air
17mm
Gauge of
Dimensions
Ceiling

Advertisement