MANUAL DE INSTALACIÓN MANUEL D’INSTALLATION MANUALE D’INSTALLZIONE MANUAL DE INSTALAÇÃO INSTALLATIONS-HANDBUCH E°XEIPI¢IO E°KATA™TA™H™ àçëíêìäñàü èé ìëíÄçéÇäÖ MH026FKEA MH035FKEA Free Joint Multi Air Conditioner (Cool and Heat) Acondicionador de aire libre del empalme multi (Refrigeración y Calefacción) Climatiseur Free Joint Multi...
Safety Precautions The following safety precautions must be taken when using your air conditioner. Risk of electric shock. • Can cause injury or death. • Disconnect all WARNING remote electric power supplies before servicing, installing or cleaning. • This must be done by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard.
Contents REPARING THE NSTALLATION Deciding on Where to Install the Air Conditioner ......... Air Conditioner and Accessories ..............NSTALLING THE NDOOR Deciding on Where to Install the Indoor Unit ..........Indoor Unit Installation ................. Purging the Unit ................... Connecting the Refrigerant Pipe ..............Cutting/Flaring the Pipes ................
REPARING THE NSTALLATION Deciding on Where to Install the Air Conditioner When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account. General Do NOT install the air conditioner in a location where it will come into contact with the following elements: Combustible gases Saline air Machine oil...
Page 5
REPARING THE NSTALLATION MH040FXEA2 / MH052FXEA2 The split type, 1-way cassette, slim duct type indoor units can be installed together. Piping outside diameter Outside diameter Power supply Unit Indoor unit Outdoor unit Ø, V, Hz Liquid MH040FXEA2 026/035 1, 220-240, 50 026/035 1/4”...
Page 6
REPARING THE NSTALLATION Deciding on Where to Install the Air Conditioner (Continued) MH068FXEA4 / MH080FXEA4 The split type, 1-way cassette, duct type indoor units can be installed together. Piping outside diameter Outside diameter Power supply Unit Indoor unit Outdoor unit Ø, V, Hz Liquid MH068FXEA4...
REPARING THE NSTALLATION Air Conditioner and Accessories Accessories in the Indoor Unit Case The following accessories are supplied with the indoor unit. The type and quantity may differ depending on the specifications. Insulation cover drain Pattern sheet Insulation refrigerant pipe Flexible hose Insulation drain Rubber...
NSTALLING THE NDOOR Deciding on Where to Install the Indoor Unit Indoor Unit There must be no obstacles near the air inlet and outlet. Install the indoor unit on a ceiling that can support its weight. Maintain sufficient clearance around the indoor unit. Make sure that the water dripping from the drain hose runs away correctly and safely.
Page 9
NSTALLING THE NDOOR Drawing of the indoor unit Unit : mm Name Remark Liquid pipe connection ø6.35 Gas pipe connection ø9.52 Drain pipe connection Power supply connection Air discharge grille Air suction grille...
NSTALLING THE NDOOR Indoor Unit Installation It is recommended to install the refnet joint before installing the indoor unit. Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity.
NSTALLING THE NDOOR Purging the Unit On delivery, the indoor unit is loaded with refrigerant gas. All this gas must therefore be purged before connecting the assembly piping. To purge the inert gas, proceed as follows. Unscrew the pinch pipe at the end of each refrigerant pipe. Result: All inert gas escapes from the indoor unit.
NSTALLING THE NDOOR Connecting the Refrigerant Pipe There are two refrigerant pipes of differing diameters: A smaller one for the liquid refrigerant A larger one for the gas refrigerant The inside of copper pipe must be clean & has no dust. Remove the pinch pipe on the pipes and connect the assembly pipes to Refrigerant oil each pipe, tightening the nuts, first manually and then with a torque...
NSTALLING THE NDOOR Cutting/Flaring the Pipes Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder). If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe. Refer to the illustrations below for examples of edges cut correctly and incorrectly.
NSTALLING THE NDOOR Performing Leak Test & Insulation Leak Test To check for gas leaks on the indoor unit, check the connection part of each refrigerant pipe by using a leak detector. Insulation Once you have checked that there are no leaks in the system, you can insulate the piping and hose.
NSTALLING THE NDOOR Drainpipe and Drain Hose Installation Care must be taken when installing the drainpipe and drain hose for Flexible the indoor unit so that condensate water is drained correctly outside. hose Drainpipe Fix the flexible hose to the drainpipe. The connection port of the flexible hose and PVC drainpipe must be fixed with PVC adhesives.
NSTALLING THE NDOOR Drainpipe and Drain Hose Installation (Continued) Lift-up Drain piping If it is necessary to increase the height of the drain hose somewhat, install a lift-up drain piping. Connect a lift-up drain pipe top to the drain hose with an adhesive for PVC.
NSTALLING THE NDOOR Connecting the Connection Cord The indoor unit is powered from the outdoor unit via the connection cord. Remove the screw on the electrical component box and remove the cover plate. Route the connection cord through the side of the indoor unit and connect the cable to terminals;...
NSTALLING THE NDOOR Wiring Wired Remote Controller (Optional) Connect the power cable, which is connected with the outdoor unit and supplied by another source, making sure that the power cable terminal should not be changed. The F3 and F4 communication cable may be cross-connected, however, it is recommended that they are connected to the corresponding F3 and F4 terminal.
NSTALLING THE NDOOR Assigning Address to Indoor Unit Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan. The address of the indoor unit is assigned by adjusting MAIN(SW02). K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 SW01 MAIN SW02 MAIN...
NSTALLING THE NDOOR Additional Functions Compensation for lost temperature in heating operation Reduces the difference between an actual room temperature and a sensed temperature by the air conditioner when heating. K5 K6 K7 K8 Switch No. Switch ON Switch OFF 2°C compensation 5°C compensation SW05...
NSTALLING THE NDOOR Bio-pure Filter Installation (Optional) The air conditioner can be fitted with a Bio-Pure or deodorizing filter to remove minute dust particles or odours. The service life of the filter is approximately three months depending on the time during which the air conditioner is used. Accessories Deodorizing Bio-pure filter...
OMPLETING THE NSTALLATION Troubleshooting Detection of errors If an error occurs during the operation, an LED flickers and the operation is stopped except the LED. If you re-operate the air conditioner, it operates normally at first, then detect an error again. LED Display on the indoor unit LED Display Indicators...
Page 23
OMPLETING THE NSTALLATION LED Display Indicators Abnormal conditions Operating Green 1. 2nd detection of refrigerant completely leak Displayed on appropriate indoor unit which is operating 2. 2nd detection of high temperature COND Displayed on outdoor unit 3. 2nd detection of high temperature DISCHARGE 4.
Page 24