Rinnai HE Series How To Use Manual page 34

Direct vent tankless water heater, temperature controllers
Table of Contents

Advertisement

Available languages

Available languages

OPTION 2:
Maximum Equivalent Vent Length Tables:
Determine the number of 90 degree elbows in the vent system. (two 45 degree elbows count as one 90 degree elbow.)
Refer to the tables below to find the maximum vent length based on the number of elbows and termination style.
Total Equivalent Vent Length (Intake/outlet) for Twin Pipe 3" PVC/CPVC
Maximum Vent Length
Termination Type
Termination Equivalent Length in feet
(meters) (Already factored into the straight
pipe lengths below)
# of 90° Elbows (each: 5 equivalent feet)
0
1
2
3
4
5
6
Total Equivalent Vent Length (Intake/outlet) for Twin Pipe 4" PVC/CPVC
Maximum Vent Length
Termination Type
Termination Equivalent Length in feet
(meters) (Already factored into the straight
pipe lengths below)
# of 90° Elbows (each: 5 equivalent feet)
0
1
2
3
4
5
6
**SW 1 in DIPSW 1 is "OFF" for lengths greater than or equal to 21 feet
Maximum vent lengths are specific to the fuel type of the tankless water heater. It is imperative when
performing equivalent vent length calculations that the gas type be taken into consideration.
24
Natural Gas Units
65 Feet
IPEX or Royal
Snorkel
Concentric Vent
Termination
Kit
20 (6.1)
15 (3.0)
Max. straight pipe vent length in feet (meters)
45 (13.7) **
50 (15.2) **
40 (12.2) **
45 (13.7) **
35 (10.7) **
40 (12.2) **
30 (9.1) **
35 (10.7) **
25 (7.6) **
30 (9.1) **
20 (6.1) **
25 (7.6) **
15 (4.6) **
20 (6.1) **
Natural Gas Units
100 Feet
IPEX Concentric
Snorkel
Vent Kit
Termination
20 (6.1)
15 (3.0)
Max. straight pipe vent length in feet (meters)
80 (24.4) **
85 (25.9) **
75 (22.9) **
80 (24.4) **
70 (21.3) **
75 (22.9) **
65 (19.8) **
70 (21.3) **
60 (18.3) **
65 (19.8) **
55 (16.8) **
60 (18.3) **
50 (15.2) **
55 (16.8) **
ATTENTION
KBD Series Manual
IPEX or Royal
Side Wall Tee
Low Profile
Termination
Termination
5 (1.5)
5 (1.5)
60 (18.3) **
60 (18.3) **
55 (16.8) **
55 (16.8) **
50 (15.2) **
50 (15.2) **
45 (13.7) **
45 (13.7) **
40 (12.2) **
40 (12.2) **
35 (10.7) **
35 (10.7) **
30 (9.1) **
30 (9.1) **
Side Wall Tee
Low Profile
Termination
Termination
5 (1.5)
5 (1.5)
95 (29.0) **
95 (29.0) **
90 (27.4) **
90 (27.4) **
85 (25.9) **
85 (25.9) **
80 (24.4) **
80 (24.4) **
75 (22.9) **
75 (22.9) **
70 (21.3) **
70 (21.3) **
65 (19.8) **
65 (19.8) **