connected please install one per Rinnai venting instructions. If a condensate line is in use, inspect the 
vent connector on top of water heater to ensure it's not stopped up. In addition; check the condensate 
drain trap and line for blockage. If stopped up remove vent pipe from unit and clean out all debris 
and/or build up from the trap or line.   
  
18. Check to ensure all two stages regulators are installed at least six foot away from appliance. Ensure 
when appliance shuts off the pressure from the two stage regulator doesn't exceed the maximum inlet 
pressure for the appliance. To verify this connect your manometer up to the test port on the bottom of 
the water heater. The inlet pressures should never exceed 10 inches water column for natural gas or 
13.5 inches on propane. If it does the regulator may be defective.   
 
19. Inspect all wiring harnesses throughout unit for water or moisture in electrical connections. If any 
connections appear to be damp or wet dry them out and try to find out what is causing this.   
 
20. If using an MSA or MSB system isolate the unit giving trouble from the system during 
troubleshooting. If unit operates when isolated the issue may be in the electronic staging system (MSA 
or MSB).   
 
21. Other suggestions;   
 
a. Verify spark electrode is installed in the correct position.    
 
b. Verify all burner cassettes are in place in burner rack. Sometimes when contractors drop a unit the 
burners can shift and become dislodged. If you find the burners dislodged loose burner bracket and 
reseat them.  
 
c. Remove the four burners located under the flame rod and move them over to the high fire side of 
the burner tray. Move the four burners from the high fire side over under the flame rod. Sometimes    
condensate or debris can get down in the burners and cause turbulence inside the burner.  
 
d. Condensate, debris or a malfunctioning mechanical component inside the gas valve may be 
preventing the valve from opening correctly once in a while. Replace gas valve.  
 
e. Voltage output to gas valve from PC board could be incorrect or intermittent due to a bad 
component on PC board, replace PC board.  
    
 
 
 
 
 
 
 
 