Rinnai HE Series How To Use Manual page 179

Direct vent tankless water heater, temperature controllers
Table of Contents

Advertisement

Available languages

Available languages

 
 
1. Check burner overheat bi‐metal switch wiring harness for loose, broken or damaged 
connections from sensor back to PC board.  
 
2. Verity unit is connected to the proper type gas. Example; if a natural gas unit, should be 
connected to natural gas.   
 
3. Verify low/high fire manifold pressures are set properly. See gas pressure setting procedures for 
pressure setting at your elevation.  
 
4. Clean sensor.  
 
5. If unit was ever converted from one gas type to another, verify the conversion process was 
preform per the manufacturer's instructions and all pressures and dip switch were set to match 
the gas type unit was converted too. 
 
6. Replace sensor   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Code 57 Troubleshooting Procedure 
Burner Overheat Bi‐metal Switch 
27 