Operational Checks; Cleaning And Maintenance - Pro-Elec PELL0238 Manual

Maintained led square emergency ceiling light

Advertisement

11. Position the LED plate assembly flush into the casing and fix into position with the 4
screws. Make sure the screws are tightened.
12. Fit the diffuser into position and tighten the 4 screws.
13. Restore the power supply. The green LED should light to show the battery is being
charged.
14. In maintained mode the lamp will illuminate.
15. Perform the electrical tests specified in the Wiring Regulations (BS7671).
Main LED plate
assembly locating screws

OPERATIONAL CHECKS

Note: This equipment must be checked regularly in compliance with local regulation and
codes of practice. For your own safety, testing should occur during the day.
After installation, you should allow 24 hours for the battery pack to charge
fully before testing. Isolate the power supply and check that the lamp remains
illuminated for at least three hours. Restore the power supply.
Each day: Check that the green charging LED is lit.
Each month (short test): Isolate the power supply and check that the lamp remains
illuminated. Record the results on the test record sheet included with these
instructions.
Every six months: Isolate the power supply and check that the lamp remains
illuminated after 1 hour. Record the results on the included test record.
Once each year: Isolate the power supply and check that the lamp is still illuminated
after 3 hours. Record the results on the included test record.
Please keep these test records in a safe place. A fire officer or other authorised
person may want to see your record of inspection and testing.

CLEANING AND MAINTENANCE

Clean the product with a soft, dry cloth only. Do not use any solvents or abrasive
chemical cleaners.
The LED lamps in this product are non-replaceable.
Battery charge LED
Battery connector
Mains connector
and fuses
7
Battery
Maintained
mode link wire