YOKOGAWA SMARTDAC+ GP10 User Manual page 36

Ethernet/ip communication (/e1)
Hide thumbs Also See for SMARTDAC+ GP10:
Table of Contents

Advertisement

I/O Messages
28
Type
Alarm information of I/O
channel
(GX/GP expandable I/O 4)
(GM sub unit 4)
(GX/GP expandable I/O 5)
(GM sub unit 5)
(GX/GP expandable I/O 6)
(GM sub unit 6)
Alarm information of I/O
channel
(Continuous channel data
area)*
Alarm information of
computation channel
Alarm information of
communication channel
* The "continuous channel data area" is a special area that enables continuous reading by limiting
the number of channels of each module to 10.
For only the I/O channels on a GX/GP main unit or I/O channels on a GM main unit, this area
can be used to read data consecutively.
• There is no decimal place information.
2 bytes
Higher Lower
Status information
0
5 bits
Error code
A/D calibration
value error
RJC error
Number
Operation type Instance ID Size
4001 to 4050,
Producer
4101 to 4150
4201 to 4250,
Producer
4301 to 4350
4401 to 4450,
Producer
4501 to 4550
5001 to 5050,
Producer
5101 to 5150
5201 to 5250,
Producer
5301 to 5350
5401 to 5450,
Producer
5501 to 5550
6001 to 6050,
Producer
6101 to 6150
6201 to 6250,
Producer
6301 to 6350
6401 to 6450,
Producer
6501 to 6550
0001 to 0010,
Producer
0101 to 0110,
0201 to 0210,
0301 to 0310,
0401 to 0410,
0501 to 0510,
0601 to 0610,
0701 to 0710,
0801 to 0810,
0901 to 0910
A001 to A100
Producer
A101 to A200
C001 to C100 Producer
C101 to C200
C201 to C300
C301 to C400
C401 to C500
Reserved
area
Alarm list
0 0
0 0
4 bits
Level 4
Level 3
Level 2
Level 1
820
200 (2 x 100) INT16
821
200 (2 x 100) INT16
822
200 (2 x 100) INT16
825
200 (2 x 100) INT16
826
200 (2 x 100) INT16
827
200 (2 x 100) INT16
830
200 (2 x 100) INT16
831
200 (2 x 100) INT16
832
200 (2 x 100) INT16
835
200 (2 x 100) INT16
836
200 (2 x 100) INT16
837
200 (2 x 100) INT16
838
200 (2 x 100) INT16
839
200 (2 x 100) INT16
840
200 (2 x 100) INT16
841
200 (2 x 100) INT16
842
200 (2 x 100) INT16
Error code
Meaning
0
No error
1
Skip
2
+Over
3
–Over
4
+Burnout
5
–Burnout
6
A/D error
7
Invalid data
16
Computation error
17
Communication error
Data type
IM 04L51B01-18EN

Advertisement

Table of Contents
loading