INVT GD100
BASIC SETUP MANUAL

Advertisement

loading

Summary of Contents for INVT GD100

  • Page 1 INVT GD100 BASIC SETUP MANUAL...
  • Page 2: Product Specifications

    PRODUCT SPECIFICATIONS Model 220(-15%) 380(-15%) 380(-15%) AC input voltage (V) 220(-15%) ~240(+10%) (1PH) ~240 (+10%) ~440 (=10%) ~440 (=10%) (3PH) (3PH) (3PH) Max. DC input voltage (V) Start-up voltage (V) Lowest working voltage (V) Recommended Dc input voltage range (V) 200 - 400 200 - 400 200 - 400...
  • Page 3: Keypad Introduction

    KEYPAD INTRODUCTION Name Description Running status indicator. LED off means that inverter is in the stopping state; LED blinking means the RUN/TUNE inverter is in the parameter auto tuning sate; LED on means the inverter is in the running state. FED/REV indicator.
  • Page 4: Enhanced Functions

    BASIC SETUP SHEET FOR GD100 NB: Pump need to be off to set box GROUP 0 BASIC FUNTION GROUP 00.01 Terminal Run Command 00.03 Maximum Running Frequency 00.04 Upper Freq Limit 00.05 Minimum Running Frequency 00.11 Acceleration time 1.5 Borehole 20 Centrifugal 00.12...
  • Page 5: Advance Settings

    ADVANCE SETTINGS Dry Run Settings GROUP 15 GROUP SPECIAL FUNCTION PARAMETERS FOR PV INVERTER Current detection of underload 15.17 See setting below (Default 50) operation Setting = Drive current / motor current at 30Hz x 100 Reset Drive Factory Default Reset: GROUP 0 BASIC FUNTION GROUP 00.18...
  • Page 6 Do as follows after inverter encounter a fault First, check whether there is something wrong with the keypad. If yes, contact the local INVT office If there is nothing wrong, check function codes of P07 group, view the corresponding recorded fault parameters, and identify the actual state when the current fault occurred based on all the parameters See the following table, check for exceptions based on the specific solutions.
  • Page 7 Fault Fault type Possible cause Solution code Phase loss on the input  Phase loss or violent fluctuation  Check the input power. side occurred on input R, S, T.  Check the installation wiring.  Phase loss output occurs to U, V, ...
  • Page 8 Fault Fault type Possible cause Solution code  The load is too heavy or stalled.  Check the load and increase the detection time if the load is normal. Speed deviation fault  Check whether control parameters are set correctly. ...