XT7 breaker trip unit - RELT
set up instructions
RELT function is factory enabled.
Threshold value can to be adjusted per a performed
coordination study as applicable
XT7 EKIP Touch Trip Unit Default PIN # is: 00001
The following is a step-by-step guide for implementing RELT
settings and ensuring proper operation of the RELT function
for XT7 touch trip units.
Enter the submenu for the 2I protection by navigating to the
advanced menu.
Press the RELT Wizard button for self-configuration.
Click Yes. Click yes again.
The RELT module is correctly installed and configured.