T8 breaker trip unit - RELT set up
instructions
RELT function is factory enabled.
Threshold value cab to be adjusted per a performed
coordination study as applicable
T8 PR332/P Trip Unit Default PIN # is: 0001
Press ESC
Select «Protection»
Press Enter
Scroll down to «MM Protection»
Press Enter arrow pushbutton
Select «Enable»
Press Enter arrow pushbutton
Scroll down to «ON»
Press Enter arrow pushbutton
Scroll down to «Threshold MM»
Press Enter arrow pushbutton
Adjust the threshold using UP and Down Arrows pushbuttons
Press Enter arrow pushbutton to leave the page
Than press ESC pushbutton
Press Press Enter arrow pushbutton to «confirm» the settings