Download Print this page
Lutron Electronics PowPak RMQ-16R-DV-B Installation

Lutron Electronics PowPak RMQ-16R-DV-B Installation

Relay module

Advertisement

Quick Links

PowPak
| Installation
TM
Relay Module
Part of the Energi TriPak
Part of the Energi TriPak
Family
Family
TM
TM
RMQ-16RCCO1-DV-B
RMQ-16R-DV-B
220 - 240 V~
With SoftSwitch
and
With SoftSwitch
50 / 60 Hz 16 A
®
®
Occupancy-Status CCO
1
1
2
RMM-16R-DV-B
RMM-16RCCO1-DV-B
With SoftSwitch
and
With SoftSwitch
®
®
Occupancy-Status CCO
RMQ-5R-DV-B
RMQ-5RCCO1-DV-B
220 - 240 V~
With Occupancy-Status CCO
50 / 60 Hz 5 A
RMM-5R-DV-B
RMM-5RCCO1-DV-B
1/2 HP
With Occupancy-Status CCO
Important Notes:
Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes.
Note: Use copper conductors only.
Check to see that the device type and rating is suitable for the application.
DO NOT install if product has any visible damage.
If moisture or condensation is evident, allow the product to dry completely
before installation.
Operate between 0 °C and 55 °C.
0% to 90% humidity, non-condensing.
For indoor use only.
WARNING
Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
PowPak
TM
Relay Module
Install in center of room to
maximize RF coverage.
Radio
Powr Savr
TM
Occupancy
Sensor
10 m
Maximum
Pico
®
Wireless
Transmitter
12 m
All Wireless Transmitters must be installed within
10 m of the PowPak
Relay Module.
TM
CCO Information
• Models RMQ-5RCCO1-DV-B, RMQ-16RCCO1-DV-B,
RMM-5RCCO1-DV-B and RMM-16RCCO1-DV-B
include a dry contact closure output that provides
occupancy status to 3rd-party equipment such as
building management systems, HVAC, and VAV
controllers.
• CCO provides both normally open (NO) and normally
closed (NC) maintained-type outputs.
• CCO rated to switch resistive loads at voltages up to
24 V only. To properly control
Switching
Resistive
inductive load types such as
Voltage
Load
relays, solenoids, or motors,
0-24 V-
1.0 A
0-24 V~
0.5 A
refer to Application Note #434.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299 | U.S.A.
Required Components
For each system ensure you have:
At Least One PowPak
Relay Module.
041-352
TM
Rev. A
(Occupancy Status CCO shown)
12/2011
Load
Status
LED
Relay Toggle
HP
Advanced
Operations
Contact
Closure
Relay Module without
Output
occupancy-status CCO
also available.
(CCO)
(SELV)
PowPak
Relay Module
TM
Start Here
1
Install PowPak
TM
Relay Module
When installing a PowPak
Module, use the supplied conduit nut
and wire the module as shown.
Suggested Installation Location:
Install in center of room.
This ensures proper RF coverage of area.
If installing unit inside a junction box please
see Application Note #423.
For more information:
www.lutron.com/powpakrelay
Associate Wireless Transmitters to PowPak
2
Before beginning this step, make sure that there are no other PowPak
from other systems can be incorrectly associated to this system.
Permanently install
3
Wireless Transmitters
Link
Test
R
Note: Please consult individual
component installation guides
for information.
Need Help? www.lutron.com | +86.21.51533628
At least one Wireless Transmitter.
+
Radio Powr Savr
TM
Occupancy Sensor
(6 maximum)
220-240 V~
50/60 Hz
Relay
Red
TM
(Switched Hot)
COM
(Common)
NC
NC
NO
(Normally Closed)
(Normally Closed)
(Normally Open)
CCO operation affected only by
associated occupancy or vacancy sensors.
Room Occupied:
NO = Close NC = Open
Room Unoccupied: NO = Open NC = Close
Relay Module
TM
modules being set up within the same building. It is possible that Wireless Transmitters
TM
A
Hold the Relay Toggle
B
Hold the indicated button on a Wireless Transmitter for
button on the PowPak
6 seconds to associate the device.
TM
Relay Module for 6 seconds
Repeat for any additional Wireless Transmitters.
to enter association mode.
Hold the Relay Toggle button on the PowPak
Note: The load will flash once after each
C
step to confirm successful completion.
Relay Module for 6 seconds to save association(s).
4
Daylight Sensor setup
Calibration
Link
A
Turn lights in room on using the
Relay Toggle button on the PowPak
TM
Relay Module or an associated Pico
.
®
Press & hold "Cal." on the associated
B
Daylight Sensor for 6 seconds.
Exit room for 5 minutes to allow
C
calibration to be completed.
Note: When calibration has completed, all lights
will flash and the system will begin daylighting.
China
Link
Cal.
Test
Radio Powr Savr
Pico
Wireless
TM
®
Daylight Sensor
Transmitter
(1 maximum)
(9 maximum)
White
(Neutral)
To Load
Black
(Hot)
Conduit Nut
To 3rd Party Equipment
Note: When wiring a CCO model to
3rd-party systems, use 0.5 to 1.5 mm
solid or stranded wire.
Test
Link
TM
Tuning (Optional)
Cal.
Test
A
If it is desired to have multiple zones of
lights turn on at different daylight levels
(using multiple Relay Modules with one
Daylight Sensor) follow the Tuning procedure
described in the Daylight Sensor
(LRF4-DCRB
installation instructions.
or LRF7-DCRB)
Use the Relay Toggle button in place of the
Dimmer/Switch tap button referenced in
the document.
| 800.901.849
| +1.610.282.3800
Hong Kong
Others
Limited Warranty
Lutron will, at its option, repair or replace any unit that is
defective in materials or manufacture within one year after
purchase. For warranty service, return unit to place of
purchase or mail to Lutron at 7200 Suter Rd., Coopersburg,
PA 18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the
implied warranty of merchantability is limited to one year from
purchase. This warranty does not cover the cost of installtion,
removal or reinstallation, or damage resulting from misuse,
abuse, or damage from improper wiring or installation. This
warranty does not cover incidental or consequential damages.
LUTRON'S LIABILITY ON ANY CLAIM FOR DAMAGES
ARISING OUT OF OR IN CONNECTION WITH THE
MANUFACTURE, SALE, INSTALLATION, DELIVERY,
OR USE OF THE UNIT SHALL NEVER EXCEED THE
PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may
have other rights which vary from state to state. Some states
do not allow the exclusion or limitation of incidental or
consequential damages, or limitation on how long an implied
warranty may last, so the above limitations may not apply to
you. Lutron, , SoftSwitch and Pico are registered trademarks
and PowPak, Radio Powr Savr and Energi TriPak are
trademarks of Lutron Electronics Co., Inc.
©2011 Lutron Electronics Co., Inc.
2
Reset Factory Defaults
Note: In some instances it may be necessary to reset the
PowPak
Relay Module back to factory default settings.
TM
A
Triple-tap the Advanced Operations button, "ADV"
on the PowPak
Relay Module and hold until the
TM
LED begins to flash slowly.
B
Within 3 seconds of flashing, release and triple-tap
the button again and the LED will flash rapidly
indicating that the unit has been reset to
factory defaults.
Note: Any associations or programming previously set
up with the unit will be lost and will need to be
re-programmed.
Cal.
Test
Troubleshooting
www.lutron.com
Load does
• Ensure breaker to the PowPak
Relay
TM
not respond
Module is on.
to Wireless
• Ensure the load has been properly wired
Transmitter(s).
to the PowPak
Relay Module.
TM
• Ensure Wireless Transmitter is properly
associated to PowPak
Relay Module.
TM
• Ensure Wireless Transmitter's battery is
installed correctly.
Wireless
• The maximum number of Wireless
Transmitters have been associated
Transmitter(s)
to the PowPak
Relay Module. To
cannot be
TM
remove a previously set up Wireless
associated to
Transmitter, tap the button used for
PowPak
TM
association on the Wireless Transmitter
Relay Module.
three times, on the third tap hold for
three seconds and then tap three
more times.

Advertisement

loading

Summary of Contents for Lutron Electronics PowPak RMQ-16R-DV-B

  • Page 1 Dimmer/Switch tap button referenced in more times. Note: When calibration has completed, all lights for information. Lutron Electronics Co., Inc. | 7200 Suter Road the document. will flash and the system will begin daylighting. Coopersburg, PA 18036-1299 | U.S.A.
  • Page 2 请授权具有资质的电气人员按照全部的本地及国家电气规范进行安装。 或间接损失进行排除或限制,或者对默示保证可以存续的期 • 从这里开始 注:仅限使用铜线。 间加以限制,因此,上述限制可能不适用于您。Lutron、 、 • 检查装置的类型与等级是否符合应用要求。 SoftSwitch 与 Pico,以及 PowPak、Radio Powr Savr 与 Energi TriPak 分别是 Lutron Electronics Co. Inc. 的注册商标 • 220-240 V~ 切勿安装任何带有明显损坏的产品。 安装 PowPak 继电器模块 与商标。©2011 Lutron Electronics Co., Inc. • 50/60 Hz 如果明显可见湿气和冷凝,请将产品放置到完全干燥,方可进行安装。...

This manual is also suitable for:

Powpak rmm-16r-dv-bPowpak rmq-5r-dv-bPowpak rmm-5r-dv-bPowpak rmq-16rcco1-dv-bPowpak rmm-16rcco1-dv-bPowpak rmq-5rcco1-dv-b ... Show all