Checklist For Yearly Maintenance Of The Outdoor Unit - Daikin Sky Air Active Series Installer's Reference Manual

Hide thumbs Also See for Sky Air Active Series:
Table of Contents

Advertisement

13
|
Maintenance and service

13.2 Checklist for yearly maintenance of the outdoor unit

Installer reference guide
68
V1
A1P
3 To prevent damaging the PCB, touch a non-coated metal part to eliminate
static electricity before pulling out or plugging in connectors.
4 Pull out the junction connector X106A for the fan motor M1F in the outdoor
unit before starting service operation on the inverter equipment. Be careful
NOT to touch the live parts. (If a fan rotates due to strong wind, it may store
electricity in the capacitor or in the main circuit and cause electrical shock.)
5 After the service is finished, plug the junction connector back in. Otherwise
the malfunction code E7 will be displayed and normal operation will NOT be
performed.
For details refer to the wiring diagram labelled on the back of the service cover.
NOTICE
NEVER directly connect power supply cables to compressors (U, V, W). This can result
in a compressor burnout.
Check the following at least once a year:
Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt,
leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked
heat exchanger can lead to too low pressure or too high pressure leading to
worse performance.
Y1
C+
C–
C+
C–
AZAS100~140MUV/Y
Sky Air Active-series
4P743509-1 – 2023.08

Advertisement

Table of Contents
loading

Table of Contents