12 Maintenance and service

12.1 Overview: Maintenance and service

12.2 Maintenance safety precautions

12.3 Checklist for yearly maintenance of the outdoor unit

R32 split series
4P751614-2 – 2023.09
NOTICE
Maintenance MUST be done by an authorised installer or service agent.
We recommend performing maintenance at least once a year. However, applicable
legislation might require shorter maintenance intervals.
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
Formula to calculate the quantity in CO
refrigerant × total refrigerant charge [in kg] / 1000
This chapter contains information about:
Maintenance safety precautions
The yearly maintenance of the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
WARNING
Before carrying out any maintenance or repair activity, ALWAYS switch off the
circuit breaker on the supply panel, remove the fuses or open the protection
devices of the unit.
Do NOT touch live parts for 10 minutes after the power supply is turned off
because of high voltage risk.
Please note that some sections of the electric component box are hot.
Make sure you do NOT touch a conductive section.
Do NOT rinse the unit. This may cause electric shocks or fire.
NOTICE: Risk of electrostatic discharge
Before performing any maintenance or service work, touch a metal part of the unit in
order to eliminate static electricity and to protect the PCB.
Check the following at least once a year:
12
Maintenance and service
|
equivalent.
2
equivalent tonnes: GWP value of the
2
Installer reference guide
55