Trane Thermafit MWC Series Installation, Operation And Maintenance Manual page 86

Modular water-cooled chiller / water-to-water heat pump
Table of Contents

Advertisement

Optional Variable Frequency Drive
Table 24. Warning and alarm definitions and troubleshooting (continued)
Warning/Alarm
Description / Probable Cause
The fan warning function is an extra protective
function that checks if the fan is running/
WARNING 23,
mounted. The fan warning can be disabled in
Internal fan fault
14-53 Fan Monitor ([0] Disabled). For the D,
E, and F Frame filters, the regulated voltage
to the fans is monitored.
The fan warning function is an extra protective
function that checks if the fan is running/
WARNING 24,
mounted. The fan warning can be disabled in
External fan fault
14-53 Fan Monitor ([0] Disabled).
WARNING/ALARM
The brake resistor is not connected or not
28, Brake check
working.
failed
The maximum temperature of the heatsink
has been exceeded. The temperature fault
ALARM 29, Heatsink
will not reset until the temperature falls below
temp
a defined heatsink temperature. The trip and
reset points are different based on the
frequency converter power size.
ALARM 30, Motor
Motor phase U between the frequency
phase U missing
converter and the motor is missing.
ALARM 31, Motor
Motor phase V between the frequency
phase V missing
converter and the motor is missing.
ALARM 32, Motor
Motor phase W between the frequency
phase W missing
converter and the motor is missing.
Too many power-ups have occurred within a
ALARM 33, Inrush
short time period.
fault
WARNING/ALARM
The fieldbus on the communication option
34, Fieldbus
card is not working.
communication fault
This warning/alarm is only active if the supply
WARNING/ALARM
voltage to the frequency converter is lost and
36, Mains failure
14-10 Mains Failure is NOT set to [0] No
Function.
When an internal fault occurs, a code number
ALARM 38, Internal
defined in Table 8.3 is displayed.
fault
No feedback from the heatsink temperature
sensor. The signal from the IGBT thermal
sensor is not available on the power card. The
ALARM 39, Heatsink
problem could be on the power card, on the
sensor
gate drive card, or the ribbon cable between
the power card and gate drive card.
Overload of digital output terminal 27
WARNING 40
Overload of digital output terminal 29
WARNING 41
A–6
Troubleshooting
Check for proper fan operation.
Cycle power to the frequency converter and check that the fan operates briefly at
start-up.
Check the sensors on the heatsink and control card.
Check 2-15 Brake Check.
Check for the following conditions.
Ambient temperature too high.
Motor cable too long.
Incorrect airflow clearance above and below the frequency converter.
Blocked airflow around the frequency converter.
Damaged heatsink fan.
Dirty heatsink.
Remove power from the frequency converter and check motor phase U.
Remove power from the frequency converter and check motor phase V.
Remove power from the frequency converter and check motor phase W.
Let the unit cool to operating temperature.
Remove power from the frequency converter and check motor phase V.
Remove power from the frequency converter and check motor phase W.
Let the unit cool to operating temperature.
Check the fuses to the frequency converter and mains power supply to the unit.
Cycle power.
Check that the option is properly installed.
Check for loose or missing wiring.
It may be necessary to contact your Trane supplier or service department. Note
the code number for further troubleshooting directions.
Check the load connected to terminal 27 or remove short circuit connection. Check 5-
01 Terminal 27 Mode.
Check the load connected to terminal 29 or remove short circuit connection. Check 5-
02 Terminal 29 Mode.
ARTC-SVX010A-EN