Connecting The Network Cables - SMA Sunny Tripower X 12 Operating Manual

Hide thumbs Also See for Sunny Tripower X 12:
Table of Contents

Advertisement

SMA Solar Technology AG
2. Fit a terminal lug to the grounding cable.
3. Clean the contact surfaces of the terminal lug using a clean cloth and ethanol cleaning agent
and do not touch the contact surfaces after cleaning.
4. Connect the grounding cable to a connection point
for additional grounding or equipotential bonding
using a hexagon socket screw M5x14, a washer,
and a serrated conical spring washer (TX25, torque:
4 Nm).
6.6

Connecting the Network Cables

Danger to life due to electric shock in case of overvoltages and if surge
protection is missing
Overvoltages (e. g. in the event of a flash of lightning) can be further conducted into the building
and to other connected devices in the same network via the network cables or other data cables
if there is no surge protection. Touching live parts and cables results in death or lethal injuries due
to electric shock.
• Ensure that all devices in the same network are integrated in the existing overvoltage
protection.
• When laying the network cable outdoors, ensure that there is suitable surge protection at
the network cable transition from the product outdoors to the network inside the building.
• The Ethernet interface of the product is classified as "TNV-1" and offers protection against
overvoltages of up to 1.5 kV.
Additionally required material (not included in the scope of delivery):
☐ Network cables(see Section 6.1.8, page 38)
☐ Where required: Field-assembly RJ45 connector.
Operating manual
DANGER
6 Electrical Connection
1
2
STPxx-50-BE-en-11
45