STIEBEL ELTRON VCR 180 ECN Operation And Installation Instruction

STIEBEL ELTRON VCR 180 ECN Operation And Installation Instruction

Hide thumbs Also See for VCR 180 ECN:
Table of Contents

Advertisement

Quick Links

OPERATION AND INSTALLATION
Central ventilation unit with heat recovery
» VCR 180 ECN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VCR 180 ECN and is the answer not in the manual?

Questions and answers

Summary of Contents for STIEBEL ELTRON VCR 180 ECN

  • Page 1 OPERATION AND INSTALLATION Central ventilation unit with heat recovery » VCR 180 ECN...
  • Page 2: Table Of Contents

    10.5 Overflow apertures ��������������������������������������������� 15 Commissioning ��������������������������������������������� 15 11.1 Initial start-up ��������������������������������������������������� 16 11.2 Recommissioning ����������������������������������������������� 16 11.3 Appliance handover �������������������������������������������� 16 Settings ����������������������������������������������������� 16 12.1 Menus ������������������������������������������������������������� 16 12.2 Direct selection parameters ���������������������������������� 19 | VCR 180 ECN www.stiebel-eltron.com...
  • Page 3: Special Information

    - The power cable must only be replaced (for Symbol meaning example if damaged) by a qualified contrac- Material losses (appliance damage, consequential losses and environmen- tor authorised by the manufacturer, using an tal pollution) Appliance disposal original spare part. www.stiebel-eltron.com VCR 180 ECN |...
  • Page 4: Information On The Appliance

    The outdoor air absorbs heat taken from the extract air. This enables a large proportion of thermal energy to Note be recovered. All measurements are given in mm unless stated oth- erwise. | VCR 180 ECN www.stiebel-eltron.com...
  • Page 5: Frost Protection

    Frost prot.: The preheating coil for frost protection is switched on. on the display. Fan disable: The symbol is displayed in the event of the "Enable fan" is set to "Off". Settings Switching the appliance on f Plug the appliance into a standard socket. www.stiebel-eltron.com VCR 180 ECN |...
  • Page 6: Parameters Adjustable From The Home Screen

    4.3.2 Selecting the fan setting f Using the Touch-Wheel, select the fan setting "Stage 1" or "Stage 2". Press "OK". | VCR 180 ECN www.stiebel-eltron.com...
  • Page 7: Menus

    The fan program is now set. f In standard view, select "Time program mode". Press "OK" to activate the fan program.   Filter reset f After changing the filters, set the "Filter reset" to "On". www.stiebel-eltron.com VCR 180 ECN |...
  • Page 8   Prog. unit software   Touch boost   Air flow rate Only for qualified contractors The "Touch boost" lets you adjust the reaction speed of the Touch- Wheel and the sensor keys. | VCR 180 ECN www.stiebel-eltron.com...
  • Page 9: Switching Off The Appliance

    Description Classification in ac- Quan- cordance with ISO 16890 tity f Ensure that the direction of air flow through the filter is FMS G4 VCR 180 ECN Coarse particle ISO Coarse > 60 % (G4) correct. filter product name Description Classification in ac- Quan- cordance with EN 1822-...
  • Page 10: Troubleshooting

    Alternate operation means that, when the combustion equipment is commissioned, the mechanical ventilation system is switched off and/or cannot be started. Alternate operation must be ensured by appropriate measures, e.g. automatically enforced shutdown of the ventilation unit. | VCR 180 ECN www.stiebel-eltron.com...
  • Page 11: Appliance Description

    - The installation room must be free from the risk of frost. Acceptance must be carried out by a specialist. In case of doubt, - The appliance must be installed horizontally. you must involve an independent expert in the acceptance pro- cedure. www.stiebel-eltron.com VCR 180 ECN |...
  • Page 12: Transport

    (see chapter "Preparations / Installation site / Minimum clearances"). f Drill holes in the ceiling for mounting the appliance with threaded pins or double ended screws. f Fit the following parts onto each threaded pin in the se- quence described. | VCR 180 ECN www.stiebel-eltron.com...
  • Page 13: Air Ducts

    Carried voices should be avoided by designing the duct with separate branches to the vents. If necessary, insulate the supply air ducts, e.g. if they are mounted outside the insulated wall panel. www.stiebel-eltron.com VCR 180 ECN |...
  • Page 14: Programming Unit

    Secure the wall mounted enclosure to the flush box or to the wall using the screws provided. 10.4 Electrical connection WARNING Electrocution Carry out all electrical connection and installation work in accordance with national and regional regulations. | VCR 180 ECN www.stiebel-eltron.com...
  • Page 15: Overflow Apertures

    X11-2 +5 V DC unit, there is a risk of injury. X11-3 Do not commission the unit until the air ducts are firmly X11-4 connected to it. www.stiebel-eltron.com VCR 180 ECN |...
  • Page 16: Initial Start-Up

    The fans are deactivated in the delivered condition.   Exhaust air fan control f Set the "Enable fan" parameter to "On".   Exhaust air fan speed   Exhaust air flow rate m³/h | VCR 180 ECN www.stiebel-eltron.com...
  • Page 17 Touch boost   Prog. unit software   Air flow rate   Flow rate, stage 0 m³/h   Flow rate, stage 1 m³/h   Flow rate, stage 2 m³/h   Flow rate, stage 3 m³/h www.stiebel-eltron.com VCR 180 ECN |...
  • Page 18 "Humidity threshold". Frost protection     Temp. to enable frost protection The unit only activates frost protection if the outdoor air temper- ature drops to the value that can be set in this parameter. | VCR 180 ECN www.stiebel-eltron.com...
  • Page 19: Direct Selection Parameters

    You can remove the cover of the float module. During assembly, ensure that the bevelled side of the float magnet faces upwards. f Push the cover back onto the float module. www.stiebel-eltron.com VCR 180 ECN |...
  • Page 20 Push the fan units back into the appliance. f Reconnect the fan cables. f Fit the control panel cover. f Slide the cross-countercurrent heat exchanger back into the appliance. f Push the wedge back in again. | VCR 180 ECN www.stiebel-eltron.com...
  • Page 21: Troubleshooting

    Check the sensor of the currently selected voltage after disconnecting one fan stage. The appliance of the following sensor plugs: cannot provide humidity X15, X16, X23, X24. Replace the protection. sensor. Replace the electronic assembly. www.stiebel-eltron.com VCR 180 ECN |...
  • Page 22: Specification

    Specification 17. Specification 17.1 Dimensions and connections 1036 1113 VCR 180 ECN b07 Electrical connection Outdoor air Diameter g04 Exhaust air Diameter Extract air Diameter g06 Supply air Diameter Remote control | VCR 180 ECN www.stiebel-eltron.com...
  • Page 23 Specification 17.2 Fan diagram The graph shows the pressure drop for examples of air distribution systems. Application range Maximum fan curve Air flow rate [ m³/h ] System curves Average value, static pressure [Pa] www.stiebel-eltron.com VCR 180 ECN |...
  • Page 24 Anschluss Netz Nicht belegt Frostschutzheizung Nicht belegt Netzleitung Zuluftluefter Sensor Temp. & Luftf. ABL Netzleitung Fortluftluefter Nicht belegt Nicht belegt Ohne Funktion Interner Schwimmerschalter Ohne Funktion | VCR 180 ECN www.stiebel-eltron.com Sensor Temperatur AUL Ohne Funktion Nicht belegt Steuerleitung Fortluftluefter...
  • Page 25: Data Table

    Min. ambient conditions, installation room (temperature) °C Max. ambient conditions, installation room (temperature) °C Available external pressure at max. air flow rate Heat recovery level Further details VCR 180 ECN 239546 Maximum height for installation 2000 www.stiebel-eltron.com VCR 180 ECN |...
  • Page 26 This will not affect warranties issued by any importers. Environment and recycling We would ask you to help protect the environment. After use, dispose of the various materials in accordance with national regulations. | VCR 180 ECN www.stiebel-eltron.com...
  • Page 27 FILTER INSPECTION LOG Filters in appliance Date Filter dirty Filter cleaned Filter changed Filters in extract air/supply air apertures (if present) Date Filter dirty Filter cleaned Filter changed www.stiebel-eltron.com VCR 180 ECN |...
  • Page 28 Hungary South Africa STIEBEL ELTRON Australia Pty. Ltd. STIEBEL ELTRON Kft. STIEBEL ELTRON Southern Africa (PT Y) Ltd 294 Salmon Street | Port Melbourne VIC 3207 Gyár u. 2 | 2040 Budaörs 30 Archimedes Road Tel. 03 9645-1833 | Fax 03 9644-5091 Tel.