Controller settings
For recommended controller settings, see the section
on the controller (controller settings).
Related information
17.17 Controller (Controller settings)
17.6.10 Constant other value
Pump variant
TPE3,TPE3 D
TPE2,TPE2 D
Any other value is kept constant.
Use this control mode if you want to control a value
which is not available in the Control mode menu.
Connect a sensor measuring the controlled value to
one of the analog inputs of the pump. The controlled
value will be shown in percentage of sensor range.
50
L
Constant other value
17.6.11 Constant curve
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
You can set the pump to operate according to a
constant curve, like an uncontrolled pump. See the
figure Constant curve.
You can set the desired speed in % of maximum
speed in the range from 13 to 100 %.
H
Constant curve
Depending on the system characteristic and the duty
point, the 100 % setting may be slightly smaller than
the actual maximum curve of the pump even though
the display shows 100 %. This is due to the power
and pressure limitations built into the pump. The
deviation varies according to pump type and pressure
loss in the pipes.
H [%]
100 %
Power and pressure limitations influencing the
maximum curve
Pos. Description
1
Limited maximum curve
Constant curve
Q
1
80 %
Q [m
3
/h]