NETWORK/COMMUNICATION CABLES
AND CONNECTIONS
Use either a CAT3 or CAT5 Network/Communication cable.
Connect the network/communication cable first before
programming.
The maximum cable length between timers is 100 feet.
Connect each unit together from one communication port to
the next communication port. It does not matter which one
goes to the next one.
Ground
Communication Ports
Regen
Lock
Figure 2 NXT Circuit Board
8 • Fleck 3200 NXT
MASTER PROGRAMMING MODE
FLOW CHART
Before entering Master Programming, please
CAUTION
contact your local professional water dealer.
NOTE: Depending on current option settings, some displays
cannot be viewed or set.
Entering Master Programming Mode
1. Press and hold the Shift and Up buttons for 5 seconds.
Press the Extra Cycle button once per display until all
displays are viewed and Normal Display is resumed. Option
setting displays may be changed as required by pressing
either Up or Down button. Use the Shift button to move one
space to the left.
2. Depending on current valve programming, certain displays
may not be viewed or set.
NOTE: If the "D" button is pressed while in master
programming, no changes will be saved.
Exiting Master Programming Mode
1. Press the Extra Cycle button once per display until all
are viewed. Master Programming Mode is exited and the
normal display screen appears.
2. To exit the Master Programming Mode without saving
changes, press the Diagnostic button.
NOTE: If no keypad activity is made for 5 minutes while in
the Master Programming Mode, or if there is a power
failure, no changes will be saved, and the unit will go
back to the main display screen.
Resets
Soft Reset: Press and hold the Up and Down buttons for 25
seconds until 12:00PM (or 12:00HR) appears. This resets all
parameters except for the flow meter totalizer volume.
Master Reset: Hold the Extra Cycle button while powering up
the unit. This resets all of the parameters in the unit. Check
and verify the choices selected in Master Programming Mode.
NOTE: If the "D" button is pressed while in master
programming, no changes will be saved.
Example:
SELECT LANGUAGE:
English
ENGLISH
Options: English
Espanol
Portugues
Deutsch
Francais
Example:
SYSTEM TYPE: 4
System Type 4, Single Unit
SINGLE UNIT
Options: System 4 (single unit)
System 5 (2-4 units) Parallel Interlock
System 6 (2-4 units) Parallel Series Regeneration
System 7 (2 units) Alternating
System 9 (2-4 units) Alternating
System 14 (2-4 units) Demand Recall
Example:
VALVE ADDRESS:
Valve Address #2 (Second Control Valve) (Default)
#2
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve) (Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
NOTE: This screen will not display for System Type 4.
Example:
SYSTEM SIZE:
2 Valves in the System (Default)
2 VALVES
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
Example:
VALVE ADDRESS:
Valve Address #2 (Second Control Valve) (Default)
#2
MASTER PROGRAMMING MODE FLOW
Options: Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve) (Default)
CHART continued
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
NOTE: This screen will not display for System Type 4.
Example:
SYSTEM SIZE:
2 Valves in the System (Default)
2 VALVES
Options: 2 Valves in the System (Default)
3 Valves in the System
4 Valves in the System
Range: 2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
Example:
REGEN TYPE:
Time Clock Delayed (Default)
TIME CLK DELAYED
Options: Time Clock Delayed (System 4 Only) (Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
VALVE TYPE:
2750 (Default)
2750
Options: 2750 (Default)
2815
2850
2900
3150
3900
Stager - Notch Cam
Example:
REGENERANT FLOW:
Downflow (Default)
DOWNFLOW
Options: Downflow (Default)
Up Flow
UF Fill First
Example:
REMOTE SIGNAL
00:06:00
START: 00:06:00
(Hours:Minutes:Seconds)
Options: Off (Default)
00:00:00 (Hours:Minutes:Seconds)
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 4
Example:
DISPLAY FORMAT:
U.S. Gallons (Default)
US-GALLONS
Options: U.S. - Gallons (Default)
Eu Metric - Liters (Metric)
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
Example:
UNIT CAPACITY:
Grains (Default)
00000000 GRAINS
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
1 to 198,000 grams CaCO3 Capacity in Metric Format
NOTE: Use the Shift button to move to the left.
Example:
CAPACITY SAFETY
00% (Default)
FACTOR:
00%
Range: 0 to 50%
NOTE: Use the Shift button to move to the left.
Example:
FEED WATER
HARDNESS: 15 GPG
15 GPG (U.S. Format) (Default)
Range: 1 to 199 Grains/Gallon (U.S. Format)
20 to 1,999 miligrams CaCO3/L (Metric Format)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
Examples: Default will need to be changed before next step
[000] = (Default)
Brings 2nd valve In Service after 125 gpm
[125]
Brings 2nd valve In Service after 400 lpm
[400]
Range:
1 to 997 gpm (U.S. Format)
0.01 to 3997 lpm (Metric Format)
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to change each decimal position.
TRIP DELAY 1:
30 SECONDS
2750 (Default)
2750
Options: 2750 (Default)
2815
2850
2900
3150
3900
Stager - Notch Cam
Trip Points 1, 2, and 3 (System 14 only)
Example:
REGENERANT FLOW:
This program step selects up to three Trip Points programmed
Downflow (Default)
DOWNFLOW
on the master timer only (Valve Address #1).
Options: Downflow (Default)
Up Flow
The actual required number of Trip Points in a system is one
UF Fill First
less than the number of valves in the system.
Trip Point 1 represents the system flow rate at which a second
Example:
REMOTE SIGNAL
00:06:00
valve will be brought In Service or Standby.
START: 00:06:00
(Hours:Minutes:Seconds)
Trip Point 2 represents the system flow rate at which a third
Options: Off (Default)
00:00:00 (Hours:Minutes:Seconds)
valve will be brought In Service or Standby.
Range: 1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 4
Trip Point 3 represents the system flow rate at which a fourth
valve will be brought In Service or Standby.
Example:
DISPLAY FORMAT:
U.S. Gallons (Default)
US-GALLONS
Trip Point 1
Trip Point 2
Trip Point 3
Options: U.S. - Gallons (Default)
Eu Metric - Liters (Metric)
Range:
U.S.: Value of Trip Point
U.S.: Trip Point 2 plus
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
1 – 997 GPM
1 plus 1 to 998
1 to 999
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
Range:
Metric: Value of Trip
Metric: Trip Point 2
0001 – 3997 Lpm
Point 1 plus 1 - 3998
plus 1 - 3999
Example:
UNIT CAPACITY:
Grains (Default)
00000000 GRAINS
Trip Delays 1, 2, and 3 (System 14 only)
Options: Grains (in U.S. Format) (Default)
Grams (in Metric Format)
This program step selects each Trip Delay time that is
Range: 1 to 9,900,000 Grain Capacity in U.S. Format
addressed with each Trip Point and will be programmed on
1 to 198,000 grams CaCO3 Capacity in Metric Format
the Master timer only (Valve Address #1). The Trip Delay time
NOTE: Use the Shift button to move to the left.
represents a minimum amount of time the system flow rate
is required to be equal or greater than the Trip Points to bring
Example:
CAPACITY SAFETY
00% (Default)
a unit In Service. It also is the minimum amount of time the
FACTOR:
00%
system flow rate is required to be less than the Trip Points to
Range: 0 to 50%
remove a unit from In Service to Standby.
NOTE: Use the Shift button to move to the left.
Trip Delay 1
Trip Delay 2
Trip Delay 3
Example:
FEED WATER
HARDNESS: 15 GPG
15 GPG (U.S. Format) (Default)
Default: 30 Seconds
Range: 1 to 199 Grains/Gallon (U.S. Format)
20 to 1,999 miligrams CaCO3/L (Metric Format)
Range:
Range:
Range:
NOTE: Use the Shift button to move to the left.
30 - 99 Seconds
30 - 99 Seconds
30 - 99 Seconds
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
Examples: Default will need to be changed before next step
[000] = (Default)
Brings 2nd valve In Service after 125 gpm
[125]
Brings 2nd valve In Service after 400 lpm
[400]
Range:
1 to 997 gpm (U.S. Format)
0.01 to 3997 lpm (Metric Format)
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to change each decimal position.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to move one space to the left.
TRIP POINT 2:
gpm
Examples: Brings 3rd valve In Service after 250 gpm
[250]
Brings 3rd valve In Service after 900 lpm
[900]
Range:
Trip Point 1 + 1 to 998 gpm (U.S. Format)
Trip Point 1 + 1 to 3998 lpm (Metric Format)
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
Fleck 3200 NXT • 9
TRIP POINT 3:
gpm