Setting The Eco Mode - Huawei UPS5000-H-1200 kVA-NTN Quick Manual

Table of Contents

Advertisement

UPS5000-H-1200 kVA-NTN
Quick Guide (480 V, 100 kVA Power Modules)

2.1.4.1 Setting the ECO Mode

Prerequisites
The UPS is working in inverter mode.
Context
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Working
mode to ECO. The information indicating that the UPS works in ECO mode is
displayed on the LCD.
Step 2 Set the ECO voltage range.
Figure 2-4 ECO specifications
Step 3 (Optional) If you set ECO mode when the UPS is in bypass mode, manually start
the UPS inverter.
Issue 01 (2023-03-20)
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when
it is required.
In ECO mode, the bypass takes priority over the inverter in supplying power. If
the bypass fails, the UPS transfers to inverter mode.
Both a single UPS and a parallel system support ECO mode which ensures a
higher efficiency.
To avoid frequent transfers between ECO mode and normal mode, do not set
ECO mode when the bypass input is unstable or is sensitive to load changes.
ECO mode is not recommended when the load is less than 10%.
Before setting ECO mode, ensure that the bypass is working properly.
NO TE
If the ECO mode is set when the UPS works in inverter mode, the UPS transfers to the ECO
mode 4 minutes after the setting is complete and the conditions are met.
Copyright © Huawei Technologies Co., Ltd.
2 Single UPS Commissioning
102