Honeywell Sensepoint XCD Technical Manual page 79

Hide thumbs Also See for Sensepoint XCD:
Table of Contents

Advertisement

Sensepoint XCD Technical Manual
SPXCDHMANEN Issue 15
Appendix A - Modbus® Protocol A-2
A.1 Modbus and the Sensepoint XCD
The Sensepoint XCD gas detector may be fitted with the optional Modbus board. Information on the
Modbus Upgrade Kit can be found in chapter 14 Ordering Information. The Sensepoint XCD supports
Modbus/RTU over an RS-485 physical layer. The interface is isolated and includes a switchable 120
Ohm termination resistor. Baud rates 9,600 or 19,200 are supported with 19,200 as the default. Most of
the operations that are possible with local user interface can also be performed over the Modbus
interface.
See chapter 5.2 and 5.7 for information on installing the optional Modbus hardware. See chapter 12.3.3
Configure Menu – Set ID Settings for information on setting the Modbus baud rate and parity using the
local user interface.
The suggested polling interval is 0.2 to 1 seconds depending on cable type, length and connected nodes.