Baxi System 35/60 Installation And Servicing Instruction page 18

Gas fired wall mounted system boilers
Hide thumbs Also See for System 35/60:
Table of Contents

Advertisement

Pressure Relief Valve
Discharge Pipe
18
Fig. 16
Fig. 17
Wall Plate
8.0 Installation
8.4
Fitting The Boiler
1. Remove the sealing caps from the boiler
connections.
2. Lift the boiler using the lower edges. Engage
the slots at the top rear of the boiler on the wall
plate (Fig. 16).
3. Insert the sealing washers between the valves
and pipes on the wall plate and the boiler
connections. The rubber washers must be
used on the gas connection.
4. Tighten all the connections.
5. Secure the boiler side panels to the boiler wall
plate flanges using the screws provided (Fig. 16).
8.5
Fitting the Pressure Relief
Discharge Pipe (Fig. 17)
1. Remove the discharge pipe from the kit.
2. Determine the routing of the discharge pipe in
the vicinity of the boiler. Make up as much of the
pipework as is practical, including the discharge
pipe supplied.
3. The pipework must be at least 15mm diameter
and run continuously downwards to a discharge
point outside the building. See section 6.6 for
further details.
4. Utilising one of the sealing washers, connect
the discharge pipe to the adaptor and tighten the
nut.
5. Complete the discharge pipework and route it
to the outside discharge point.
IMPORTANT: Make all soldered joints before
connecting to the pressure relief valve.