8-4. Check Codes list

For other types of outdoor units, refer to their own service manuals.
Check code
Outdoor 7-segment display
Controller
Check
Sub-code
code
C05
C06
C12
E01
E02
E03
E04
Location
Description
System status
of
detection
Central
Central control
Continued
control
device
operation
device
transmission
trouble
Central
Central control
Continued
control
device reception
operation
device
trouble
General-
Batch alarm
Continued
purpose
for general-
operation
device
purpose
I/F
device
control interface
Remote
Indoor-remote
Stop of
controller
controller
corresponding
communication
unit
trouble
(detected at
remote
controller end)
Remote
Remote
Stop of
controller
controller
corresponding
transmission
unit
trouble
Indoor unit
Indoor-remote
Stop of
controller
corresponding
communication
unit
trouble
(detected at
indoor end)
Indoor unit
Indoor-outdoor
Stop of
communication
corresponding
circuit trouble
unit
(detected at
indoor end)
- 182 -
Check code detection
Check items (locations)
condition(s)
Central control device is
• Check for failure in central
unable to transmit signal.
control device.
• Check for failure in central
control communication line.
• Check termination
resistance setting.
Central control device is
• Check for failure in central
unable to receive signal.
control device.
• Check for failure in central
control communication line.
• Check terminator resistor
setting.
• Check power supply for
devices at other end of
central control
communication line.
• Check failure in P.C.
boards of devices at other
end of central control
communication line.
Trouble signal is input to
• Check trouble input.
control interface for general-
purpose devices.
• Check remote controller
Communication between
indoor P.C. board and
inter-unit tie cable (A/B).
remote controller is
• Check for broken wire or
disrupted.
connector bad contact.
• Check indoor power
supply.
• Check for failure in indoor
P.C. board.
• Check remote controller
address settings
(when two remote
controllers are in use).
• Check remote controller
P.C. board.
Signal cannot be transmitted
• Check internal
from remote controller to
transmission circuit of
remote controller.
indoor unit.
--- Replace remote
controller as necessary.
There is no communication
• Check remote controller
from remote controller
and network adaptor
(including wireless) or
wiring.
network adaptor.
Indoor unit is not receiving
• Check order in which
signal from outdoor unit.
power was turned on for
indoor and outdoor units.
• Check indoor address
setting.
• Check indoor-outdoor tie
cable.
• Check outdoor terminator
resistor setting (SW100,
Bit 2).