Next, refer to the following table below, calculate the corrective amount of refrigerant according to system
diversity (D)
Corrective amount of refrigerant varies according to the system diversity (D)
Diversity D(%)
Corrective amount
of refrigerant (Ibs)
50% ≤ D < 60%
-5.51
60% ≤ D < 70%
-4.41
70% ≤ D < 80%
-3.31
80% ≤ D < 90%
-2.2
90% ≤ D < 95%
-1.1
95% ≤ D
Lastly, add the corrective amount of refrigerant according to system diversity (D), the corrective amount of
refrigerant according to indoor unit capacity (C) and the additional amount of refrigerant by the pipe
diameter on liquid side and the pipe length (B) to the compensation amount of refrigerant according to total
outdoor unit capacity (A)
This is the final additional amount of refrigerant.
If a minus sign is indicated as the result, the additional amount of refrigerant is zero (0) Ibs, do not reduce
the refrigerant.
Compensation amount of refrigerant according to total outdoor unit capacity (A)
Additional amount of refrigerant by pipe length (B)
Corrective amount of refrigerant according to indoor unit capacity (C
Corrective amount of refrigerant according to system diversity (D)
Total additional amount of refrigerant
0
- 107 -
Ibs
Ibs
Ibs
Ibs
Ibs