Wave Tool Advance For Smms-U Series; Before The Use Of Wave Tool Advance; About Wave Tool Advance; Valid/Prohibition/Permission Setting For Test Operation From Wta App - Toshiba MMY-MUP0961HT6P-UL Service Manual

Hide thumbs Also See for MMY-MUP0961HT6P-UL:
Table of Contents

Advertisement

7-8. Wave Tool Advance for SMMS-u Series

7-8-1. Before the Use of Wave Tool Advance

Wave Tool Advance (WTA) is an application for the Android OS or iOS smartphone.
You can use this application to check system capacity, to make a test operation, to get a test operation result,
and to make a simple report.
Please move to the following URL(or QR Code), and confirm
"Objective product list" and "Smartphone model & OS Version".
After confirmation, download/install the Wave Tool Advance Application (WTA App.) and USER GUIDE.
Be sure to read the USER GUIDE before the use of this application.
<Wave Tool Advance Support URL>
https://www.toshiba-carrier.co.jp/global/appli/smms_wave_tool_advance/index.htm
Notice
WTA App. is not supported SMMS-e series. Please use the "SMMS Wave Tool" when using the SMMS-e series.
You can download and install "SMMS Wave Tool" from the following URL.
<SMMS Wave Tool Support URL>
https://www.toshiba-carrier.co.jp/global/appli/smms_wave_tool/index.htm

7-8-2. About Wave Tool Advance

This application is the NFC(Near Field Communication) function of
smartphone.
When it is used, make sure that the NFC antenna on the
smartphone is aligned with the "TOUCH "mark on the NFC tag.
• Refer to the USER GUIDE of the Wave Tool Advance for the details.

7-8-3. Valid/Prohibition/Permission setting for Test operation from WTA App.

• WTA App Test operation function enables setting within 48 hours elapsed from outdoor unit power ON. If
Power ON time is over 48 hours, it can not use WTA App test operation. (Other WTA App function can be
used.)
• You should decide whether to make use of this test operation function at its own responsibility and also be
sure to confirm notices in the Operating Manual before performing the test operation.
• If you want to prohibit the test operation from WTA App, perform the following steps.
* High voltage parts exist in the electrical control box. If you set switch setting, set it from the access door
cover of the electrical control box cover to avoid electric shock.
After finishing steps, slide the access cover to the position before and fix it with the screw.
• Refer to following table for setting change of the test operation function to be effective after 48hours.
Access cover
Control box cover
Relationship with Power ON time and Test operation function.
Until 48 hours elapsed from the outdoor unit power ON,
Validness
WTA App can start a test operation. After 48 hours, it
cannot.
Regardless of the elapsed time, WTA App cannot start a
Prohibition
test operation.
Regardless of the elapsed time, WTA App can start a test
Permission
operation.
Push switch
Fixing screw
7-segment
display
Rotary switch
Status
- 169 -
Wave Tool Advance
NFC tag
Outdoor Unit
2,4,6
3,5
SW04
SW05
SW06
SW01
SW02
SW03
7-segment display
at O.DN Code
No.05
d.⌴⌴⌴0
d.⌴⌴⌴1
d.⌴⌴⌴2
System Info.
Site Name
-
Model Name
-
Serial No.
-
-
Unit No/HP(Ton)
Star. Prio.
-
Defrost Gr.
-
Line Address
-
-
Mode
Wave Tool
Check Code
-
Advance
Notice Code
-
Unit
-
Smartphone
with WTA App.
3,5
1-7
1,7