4.3.5 System Setup Menu
4.3.6 Basic Setup Menu
4.3.7 Battery Setup Menu
This is System Setup page.
This is Basic Setup page.
Lithium Battery
Batt Mode-------- Lithium
Max A charge-------- 0-185A Max
A Discharge-----0-185A Activate
Battery------Enable AGM Battery
Batt Mode-------- Lithium
Batt Capacity-------- 50-2000Ah
No Batt --- No need to set other parameters, keep the
default value.
This is Battery Setup page
Start =30%---It indicates that the Generator will start when
the Battery capacity is less than 30% in the condition of
Off-grid mode.
A= 40A---It indicates the Current that the Generator
charges the Battery after started.
Gen Charge---The Switch that the Generator charges the
Battery.
Gen Signal ---It indicates whether the Generator's ATS
signal is on.
Max Run Time (x.x hous) Indicates that the generator is
the longest in a day, the time x.x hours can be run, and
the generator will be turned off when the time is up.
24.0hours (default) means that It keeps running without
shutting down.
Down Time (x.x hours) It indicates the delay of the
Generator to shut down after it has reached the run
time