Current monitoring

Advertisement

TM
opEration
The H749 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in the conductor's amperage that crosses
the adjustable switch threshold plus the hysteresis value causes the resistance of
the FET status output to change state, similar to the action of a mechanical switch.
In this model, the setpoint is adjustable through the action of a twenty (20) turn
potentiometer (see the CALIBRATION section). An integrated relay allows start/
stop control. The status output is suitable for connection to building controllers or
other appropriate data acquisition equipment operating at up to 120 volts. The H749
requires no external power supply to generate its output.
notEs
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product's maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.
Z201491-0A
PAGE 2
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
H749
> 135 A (Sensor max.)
240A
5A
300A:
H68xx-5A CT
< 1 A (Sensor Min.)
4x
0.5A
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
INSTALLATION GUIDE
Calibration
Before beginning calibration, establish normal load conditions.
OK!
A
Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
!
OK!
A
1. Turn setpoint screw
clockwise until Status OPEN
LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status CLOSED LED just
turns ON.
Status
Setpoint
Closed
STOP
B. To monitor over-current (mechanical problems, seized impeller)
!
OK!
A
1. Turn setpoint screw
counter-clockwise until Status
CLOSED LED turns ON.
2. Slowly turn the setpoint screw clockwise until the Status OPEN LED just turns ON.
Status
Open
Setpoint
STOP
troublEshooting
Problem
No Reading at Controller
• Check sensor calibration (see above)
• Check for control voltage at sensor (<120 V)
• Check for amperage in monitored conductor (>1 A)
Setpoint screw has no
The setpoint screw has a slip-clutch at both ends of its travel to
stops
avoid damage. Twenty turns CCW will reset the sensor to be
most sensitive. Repeat calibration above.
Both LEDs are lit
Setpoint screw is too far clockwise. See solution above.
STATUS
OK!
Status
Setpoint
Open
STOP
3. Turn the screw an
Setpoint
+
additional 1/4 turn
counter-clockwise for
1/4
operational margin.
STATUS
OK!
Status
Setpoint
Closed
STOP
+
3. Turn the setpoint
Setpoint
screw an additional
1/4 turn clockwise for
1/4
operational margin.