Figure 6-2: Configure Digital I/O 1 as a Digital Input
12. Click Send.
13. On the PCCU navigation tree, expand TFIO 8/HSPC I:00. Then select Advanced.
14. Select the Pulse Input tab.
15. Under the Wetting Current/Pullup Enable section, select the value field next to the point. In
this example, the point is identified as DI1.
16. Select Enabled from the drop-down list.
17. Click Send.
Figure 6-3: Pulse Input Wet Current/Pullup configuration
18. Select the I/O Pin tab.
19. Click on the value field next to Field Voltage Selection, and then select: Use External from
the drop-down list
20. Click Send.
Figure 6-4: HSPC module configuration for External power mode
7

Verify output from CoriolisMaster

This procedure describes how to verify that the CoriolisMaster is transmitting digital output signals to
the HSPC module. Verification is done from the CoriolisMaster local display. For detailed instruction to
8 | HS PC CO N FI G U RATI ON G UI D E | 21 08 7 44M N A A
(Figure
6-4).